Eaton TPC2234-A User Manual
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999
2
RACK MOUNTED
•
19” x 1U (1.72”) x 4.5”
•
Approximate shipping weight: 5 lbs.
EMI/RFI FILTER
•
Add “F” to part number (optional)
•
Differential Mode - Line to Line
•
Common Mode - Line to Ground
SPIKE/SURGE SUPPRESSION
•
L-N, L-G, N-G (add “F” to p/n)
OVERLOAD CIRCUIT PROTECTION
•
Electromagnetic breaker
provides manual on/off switching and
trips in an overload condition
provides manual on/off switching and
trips in an overload condition
DUAL POWER INPUT
•
Two provided on rear panel with plug
•
240V~ systems do not come standard
with a plug but are available as an option
with a plug but are available as an option
NOTE: Both power sources must be
in-phase. Out-of-phase sources can
cause severe damage.
in-phase. Out-of-phase sources can
cause severe damage.
(See the T2235 for out of phase switching)
INDICATOR LIGHTS
•
(1) Main Power indicator light
•
(1) Primary Power available
•
(1) Secondary Power available
OUTLETS
•
Rear panel has (8) NEMA style outlets
•
All outlets are switched together
TRANSFER/RESPONSE TIME
•
The TPC2234s will auto-switch to
secondary power when the primary
source fails. When the primary source is
back on line, the system will auto-switch
from the secondary source back to the
primary.
secondary power when the primary
source fails. When the primary source is
back on line, the system will auto-switch
from the secondary source back to the
primary.
•
120V~: nominal is 115V~, pull-in is
92.0V~ and dropout is 46.0V~
•
240V~: nominal is 240V~, pull-in is
192.0V~ and dropout is 96.0V~
•
Response time from Primary Source to
Secondary Source is 20ms depending
on load
Secondary Source is 20ms depending
on load
•
Response time from secondary source
back to primary is about 15-20ms
back to primary is about 15-20ms
SPECIFICATIONS
TPC2234-A
TPC2234-A-F
TPC2234-A2
TPC2234-A2-F
TPC2234-B
TPC2234-B-F
Approvals
UL/cUL
UL/cUL
UL/cUL
UL/cUL
UL/cUL
UL/cUL
Voltage Input/Output (50/60Hz)
120V
120V
120V
120V
240V
240V
Current Input
15A
15A
20A
20A
15A
15A
Current Output
12A
12A
16A
16A
12A
12A
Full Load VA
1440VA
1440VA
1920VA
1920VA
2880VA
2880VA
Circuit Breaker
15A
15A
20A
20A
15/15A
15/15A
NEMA Outlets (8) rear
5-15
5-15
5-20
5-20
6-15
6-15
Surge Suppression (add “F” to p/n)
N/A
YES
N/A
YES
N/A
YES
EMI/RFI Filter (add “F” to p/n)
N/A
20A
N/A
20A
N/A
20A
Surge Suppression (add “F” to p/n)
150V
150V
150V
150V
270V
270V
(2) Power Cords/Length
14/3, 9’
14/3, 9’
12/3, 9’
12/3, 9’
14/3, 9’
14/3, 9’
(2) Plugs
5-15P
5-15P
5-20P
5-20P
N/A
N/A
Auto-Switching Between Primary and Secondary Power
TPC2234 Front
TPC2234 Rear
HOLE SPECIFICATION TABLE
Rack Mounting Hole Specification Table
19.00”
Y
A
Z
A
Y
Z
1.75
.25
1.25