APC 125KVA PDU w/ 480 PRI 208/120 SEC K 13 XMER PD125G6FK13 User Manual

Product codes
PD125G6FK13
Page of 72
SPDU Technical Handbook
7
Section 2: Technical Specifications
Overview of SPDU offerings
Standard features. 
APC’s Stationary Power Distribution Unit (SPDU) combines power 
distribution with isolation and flexibility. A provision for top and bottom cable feed is standard. 
Other features include 100% front accessibility, K1-K20 isolation transformers/shielding, and two 
panel boards with up to 84 pole positions (or any of three panel board alternatives that allow sub-feed 
breakers to be incorporated into the mix).
Input. 
Output. 
Physical. 
Environmental. 
Rated Power kVA:
75, 100, 125, 150, 200, 225, 300
Nominal Input Voltage:
60 Hz @ 208V/480V/600V
K Factor:
K1, K13, K20
Efficiency at Full Load:
96.5 - 98%
Harmonic Distortion:
< 1%
Nominal Impedance:
3 - 5%
Main Incoming Breaker:
65,000 AIC @ 208V / 35,000 @ 480V / 18,000 @ 600V
Nominal Output Voltage:
208V / 120V
Panel Board Section (choice of):
• Two 42-pole panel boards
• One 42-pole panel board and up to (7) 225A sub-feed breakers
• One 42-pole panel board and up to (3) 400A sub-feed breakers
• Up to (11) 225A sub-feed breakers
Maximum Height Dimensions:
81.5 inches (207.01 cm), 
includes removable 5.5-inch (13.97) top box
Maximum Width Dimensions:
36 inches (91.44 cm) for 75 - 225 kVA
45 inches (114.30 cm) for 300 kVA
Maximum Depth Dimensions:
32 inches (81.28 cm) for 75 - 225[K13] kVA
38.5 inches (97.79 cm) for 225[K20] and all 300 kVA
Standard Color:
Black
Units per Pallet:
1 with maximum of two sidecars
Operating Environment:
0 - 40°C (32 - 104°F)
Operating Relative Humidity:
0 - 95%, non-condensing
Audible Noise:
50-55 decibels
Protection Class:
NEMA 1
UL Certification:
UL60950