APC 100KVA PDU w/ 480 PRI 208/120 SEC K 1 Rated XMER PD100G6FK1 User Manual

Product codes
PD100G6FK1
Page of 72
Section 2: Technical Specifications
8
SPDU Technical Handbook
Individual product SKUs
PD75G6FK1
Input. 
Output. 
SPDU physical. 
Sidecar physical. 
Environmental. 
Nominal Input Voltage:
480V, 3PH
Input Frequency (Hz):
60 Hz, +/- 3 Hz
Transformer Type:
K1
Efficiency:
96%
Main Breaker Rating:
125A
Maximum Input Current:
90A
Load Capacity:
75 kVA
Nominal Output Voltage:
208V / 120V
Full Load Heat Output:
12276 BTU/hr
Impedance:
4.50%
Voltage Regulation:
4.52 @ .8 power factor, 3.39 @ 1.0 power factor
Transformer Taps:
2 @ 2.5% full capacity above nominal, 
4 @ 2.5% full capacity below nominal
Net Height:
81.5 inches (207.01 cm), 
includes removable 5.5-inch (13.97 cm) top box
Net Width:
36 inches (91.44 cm)
Net Depth:
32 inches (81.28 cm)
Net Weight:
1270 pounds (576.06 kg)
Standard Color:
Black
Net Height:
81.5 inches (207.01 cm), 
includes removable 5.5-inch (13.97 cm) top box
Net Width:
20 inches (50.80 cm)
Net Depth:
32 inches (81.28 cm)
Net Weight:
520 pounds (253.87 kg)
Standard Color:
Black
Operating Environment:
0 - 40°C (32 - 104°F)
Operating Relative Humidity:
0 - 95%, non-condensing
Audible Noise:
50 decibels
Protection Class:
NEMA 1
UL Certification:
UL60950