Brick Replacement
PRECAUTIONS
 
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
·  Apply appropriate personal protective equipment (PPE) and follow safe electrical work  
  practices. See NFPA 70E.
·  This equipment must only be installed and serviced by qualified electrical personnel.
·  Turn off all power supplying this equipment before working on or inside equipment.
·  Always use a properly rated voltage sensing device to confirm power is off.
·  Replace all devices, doors and covers before turning on power to this equipment.
Failure to follow these instructions will result in death or serious injury.
Surge Protective Devices (SPD)
Retain for future use
For technical support, go to www.apc.com/support/contact
WARRANTY
For warranty information about your Surge Protection Device, go to the APC
Choose your part number from among the three categories listed under
Hardwire Surge Suppression. A screen containing information specific to
tab to locate the file containing your warranty.
Web site: 
www.apc.com. Choose Products, and then choose Surge Protection
and Power Conditioning. Scroll down to Hardwire Surge Suppression.
your Surge Protection Device is then displayed. Click on the 
Documentation
INSTALLATION
Verify that all brick replacement modules have the correct catalog number. The catalog number
is found on the nameplate of each brick replacement module (see Figure 1) and on the SPD
device nameplate.  Use Table 1 to determine the correct replacement catalog number based on
the existing SPD system voltage and peak surge current rating.
SYSTEM  
VOLTAGE
PEAK SURGE  
CURRENT  
RATING
PRODUCT 
NUMBER
120/240V, 1 phase, 3 wire Wye 
120 kA
120 kA
BMP3-A
120/208V, 3 phase, 4 wire Wye 
220/380V, 3 phase, 4 wire Wye 
277/480V, 3 phase, 4 wire Wye 
347/600V, 3 phase, 4 wire Wye 
BMF3-A
BMH3-A
BMG3-A
BML3-A
120 kA
120 kA
120 kA
Table 1: Brick Module Replacements
Table 2: Installation Torque
Power Connection
Terminal Torque
W/O Disconnect
W/ Disconnect
AØ, BØ, CØ & N
35 lb-in (4N·M)
50 lb-in (5.7N·M)
Ground
50 lb-in (5.7N·M)