Option 3: Environmental-Strapping
This provides for external temperature, humidity and contact closure environmental sensing. An optional temperature and humidity probe can be 
ordered separately to read temperature at two locations and humidity at one location. The contact closure can be connected to any standard 
normally-open or normally-closed switch, such as a cabinet door or water sensor switch. There is the capability to set thresholds and receive either 
e-mail alerts or SNMP traps to notify the user of events.
Strapping allows for multiple IPV units to be connected together in an RS485 serial configuration. Standard network cables are used to 
interconnect Pulizzi IPV units. Up to 23 units can be connected to one master controller. ONLY the master controller is required to 
have a network connection. The other devices are accessed through the master unit via serial, telnet, or web interfaces.
Power Monitoring / Current Metering
This allows for power monitoring of both current and voltage. The voltage is only displayed in the software interface. The current meter is a true 
RMS meter capable of 0.1A resolution. This allows the user to properly load balance the power distribution unit. Thresholds can be set for over/under 
current and voltage. The unit can send e-mail alerts or SNMP traps to alert the user of the condition. In addition, outlet on/off actions can be 
performed based off the thresholds.
Option 4: Local Current Meter Display
A local two digit LED display outputs the total current per section. For units with more than one 8-outlet section, the display cycles between sections. 
The super-bright large digit display can be read from up to 20 feet away.
Option 5: Cable Length/Plug Type
The IPV has two options for attached power cable length, 9 feet or 15 feet. The user can also select a straight blade or twist lock plug for power input. 
Only the AB versions are available with IEC C20 inlets. Several power cable options are available for North American and European use. The power 
cables must be ordered separately.