Eaton PW103SW2U413 User Manual

Page of 6
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999 
3
CHASSIS
19” x 1.72” (1U) x 9.5”
Weight approximately 12 lbs. 
(IPC3401 & 02)
Weight approximately 15 lbs. 
(IPC3402-2756
& IPC2930)
Detachable mounting brackets allow for 
several mounting options
NEMA or IEC 320 OUTLETS
IPC3401 has 8 IEC 60320 Type C13
– Rated by UL/CSA 125V~/15A
– Rated by UL/CSA/VDE 250V~/10A
IPC3402 has 8 NEMA 5-15R
IPC3402-A2 has 8 NEMA 5-20R
IPC3402-2756 has 4 NEMA 5-20R 
and 4 NEMA 5-15R
IPC3402-2930 has 8 NEMA 5-15R
(11) INDICATOR LIGHTS
Main power to system-CB “on”
Individual power “on” to outlets 1-8
Data acquisition and remote disable
REMOTE or LOCAL CONTROL
Serial RS232 port (DB9 Male) for direct 
computer or modem connection
RS485 input/output for strapping up to 
10 systems together over CAT.5 cable
Local: one on/off switch for each outlet
-NET SYSTEMS ONLY: RJ45 for 
network connections (Ethernet)
REMOTE DISABLE
With the push of a button, disable 
remote access to the IPC when needed
POWER SUPPLY
The IPC3401 series features a full range 
power supply for operation at 
100-240VAC input/output
BAUD RATE
Default: 9600 baud
EMI/RFI FILTERING
Common Mode - Line to Ground
Differential Mode - Line to Line
Filtered inlet isolates noise before 
entering the system
IPC3402-2756 and IPC3402-2930 
do not have filtering
SPIKE/SURGE SUPPRESSION (TVSS)
Line to Line 
Multi-stage, both MOVs and SAPs
BRANCH CIRCUIT PROTECTION
UL498 Listed Main Disconnect Breaker 
and guard, with a long time delay curve 
provides manual on/off switching and 
trips in an overload condition
POWER INPUT
IEC 60320 Type C20 EMI/RFI Filtered Inlet
Mating power cables must be ordered 
separately
IPC3402-2756: attached 10’ cable and
NEMA L5-30P
OUTLET STATUS
Query the IPC for Outlet and Watch Dog 
status, i.e. outlets are “on” or “off”
STRAPPING
Strapping allows up to 10 IPCs 
(80 outlets) to be controlled at one address
Units are connected together via the 
RS485 “IN” and “OUT” connectors
UNIT NAME / PASSWORD
The IPC comes with a default name 
@@@@, which can be changed to 
any four alphanumeric characters
Optional 3 character password
MULTIPLE TIME DELAY
TM
(MTD
TM
)
Sequence power up and power down to 
outlets with a one second time delay 
(factory set)
User Programmable:
– Set power “on” sequence to any 
  combination 
of 
outlets
– Set the MTD
TM
timing from 1 second 
 
  to 999 seconds, i.e. 009 = 9 seconds
AUTO-EVENT COMMAND RESPONSE
The IPC will automatically update the status 
of outlets (“on” or “off”) via serial or telnet
SOFTWARE CONTROLS
Multi-platform compatible
Control via Terminal Emulation Software
Web interface for browser control
COMMANDS AVAILABLE
All outlets on/off
Specific outlets on/off
Set up and Sequence on/off all outlets
Create password and unit address
Outlet naming (8 characters)
Set up, enable or disable Watchdog
Display outlet and Watchdog Timer status
Automatically receive update outlet 
status whenever there’s a change
Auto-reboot outlet 1 with a five second 
delay on restart
SPECIFICATIONS:
IPC3401
IPC3401-NET
IPC3402
IPC3402-NET
IPC3402-A2
IPC3402-A2-NET
IPC3402-2756
IPC3402-2930
Approvals
UL/cUL, CE, GS, FCC
UL/cUL, FCC
UL/cUL, FCC
UL/cUL, FCC
UL/cUL, FCC
UL/cUL
UL/cUL
Voltage (50/60Hz)
100-240V~
100-240V~
120V~
120V~
120V~
120V~
120V~
120V~
Current Input
20A @ 120V~  
16A @ 240V~
20A @ 120V~  
16A @ 240V~
20A
20A
20A
20A
30A
30A
Current Output
16A
16A
16A
16A
16A
16A
24A
24A
Full Load VA
1920VA @ 120V~
3840VA @ 240V~
1920VA @ 120V~  
3840VA @ 240V~
1920VA
1920VA
1920VA
1920VA
2880VA
2880VA
Outlets (IEC or NEMA)
Type C13
Type C13
5-15R
5-15R
5-20R
5-20R
(4) 5-20R, (4) 5-15R
(8) 5-15R
Circuit Breaker
20/20A
20/20A
20A
20A
20A
20A
20/10A
20/10A
EMI/RFI Filter
20A
20A
20A
20A
20A
20A
N/A
N/A
Surge Suppression
270V
270V
270V
270V
270V
270V
270V
270V
Power Input
Type C20 Inlet
Type C20 Inlet
Type C20 Inlet
Type C20 Inlet
Type C20 Inlet
Type C20 Inlet
L5-30P
L5-30P
Power Cord
Power cables must be ordered separately.
10/3AWG 10’
10/3AWG 10’
Ethernet Control
NO
YES
NO
YES
NO
YES
YES
YES
Serial Control (RS232)
YES
YES
YES
YES
YES
YES
YES
YES