Minute Man RPM2001 Leaflet
© Copyright 2007, Para Systems, Inc. Product specifications are subject to change
without notice. Minuteman and Minuteman Platinum Protection Plan are registered
trademarks of Para Systems, Inc.
PN-34000
185
- 09-09
From Para Systems, Inc.
Power Technologies
Para Systems, Inc./Minuteman UPS
1455 LeMay Drive, Carrollton, TX 75007 U.S.A.
Phone 800.238.7272 +1 972.446.7363 Fax +1 972.446.9011
Model Number (230 VAC Specs in
parenthesis)
RPM 1600
Client (RPM
1600i Client)
RPM 1601
(RPM 1601i)
RPM 1609 (RPM
1609i)
RPM 2000
Client
RPM 2001
RPM 2009
Direct NT PC connections
None
8 each RJ- 11
/ RS-232
None
8 each RJ-11 /
RS-232
Smart telephone call-in
function
Yes
Net control / Support
HTTP server & SNMP agent TCP/IP, MIBS
Dimensions H X W X D
1.75 X 17.00 X 6.50 in. (44.45 X 432 X 165.1mm)
Net weight • Ship weight
6 lb (2.7 kg) • 7 lb (3.2 kg)
8 lb (3.6 kg) • 9 lbs (4.1 kg)
Input Connection
NEMA 5-15P (IEC 320)
NEMA 5-20P
Output receptacle quantity
and Type
8 each NEMA 5-15R (IEC 320)
8 each NEMA 5-15R
LAN connection • Driver
console connection • Driver
RJ-45 • Ethernet, DB9 • PPP + Dial-In
2nd RPM connection (Daisy link
connection)
RJ-11, Connect Up To 15 Additional RPMs
Ring on / Reset / Off
Yes
Nominal • Input voltage range
115 VAC Nominal • Range 85 - 145 VAC (230 VAC Nominal • Range 170 - 290 VAC)
Input frequency
44-66Hz Full Range
Maximum output
15 Amps
20 Amps
Input protection
15-Amp Circuit Breaker
20-Amp Circuit Breaker
Spike / Surge protection
IEC 801-2, 801-3,801-4,801-5
Surge energy rating
950 Joules
Testing standards
IEEE / ANSI C62.45
Operating temperature
0 To 40°C
Storage temperature
-15 To 50°C
Relative humidity
0-95 % Non-condensing
Altitude
10,000 ft (3,000 m) without derating
Minuteman® Remote Power Manager (RPM) Specifications
SNMP
SNMP
SNMP
Front View
Back View
Smart
Phone
control
via
telephone
Control via
web browser
or set up telnet
Daisy-chain up to 15
additional RPM units to
control 128 devices
additional RPM units to
control 128 devices
RS-232 port
for setup
Plug UPS into utilityAC mains.
Using a UPS with the Minuteman RPM
is recommended but not required.
Minuteman
Endeavor UPS Series
Endeavor UPS Series
Battery Pack
Switch
Router
Bridge
Server #1
Server #2
AC Power
Communications
Communications
To
LAN
ENV
Sample
Installation Diagram of Minuteman
®
RPM
AC Input
Power
AC Outlets
RJ-11 to RS-232
Server Shutdown
RJ-11
Smart
Phone
Interface
RJ-11
Daisy
Chain
Connection
RS-232
Port to
PC or
Modem
RJ-45
Ethernet
Connection
AC
Power
Switch
Outlet
Control
Buttons
ENV
Components of Minuteman
®
RPM