Netgear RNRX442E – ReadyNAS 1500, 8TB NETWORK STORAGE (4 x 2 TB) Hardware Manual

Page of 57
ReadyNAS 3100
22
NETGEAR ReadyNAS Rack-Mount Storage Systems 
Rack-Mount Setup
Use the rack-mount hardware included with your ReadyNAS 3100 to install it in a rack. Read 
the 
 section in Appendix A.
Considerations
Keep the following considerations in mind as you install your unit:
•     
Ambient operating temperature. If the unit installed in a closed or multi-unit rack 
assembly, the ambient operating temperature of the rack environment might be greater 
than the ambient temperature of the room. Therefore, consideration should be given to 
installing the equipment in an environment compatible with the maximum rated ambient 
temperature found in 
25
•     
Reduced airflow. Mount the equipment into a rack so that the amount of airflow required 
for safe operation is not compromised.
•     
Mechanical loading. Mount the equipment into a rack so that a hazardous condition 
does not arise due to uneven mechanical loading.
•     
Circuit overloading. Consider the equipment’s connection to the power supply circuitry 
and the effect that any possible overloading of circuits might have on overcurrent 
protection and power supply wiring. Consider equipment nameplate ratings when 
addressing this concern.
•     
Reliable ground. This product requires that a reliable ground be maintained at all times. 
To ensure this, ground the rack itself. Pay particular attention to power supply 
connections other than the direct connections to the branch circuit (for example, the use 
of power strips).
•     
Setup location. This product is intended for installation in a restricted access location 
(dedicated equipment rooms, service closets, and the like) only.
•     
Clearance. Leave enough clearance in front of the rack (about 25 inches) to enable you 
to open the front door completely and in the back of the rack (about 30 inches) to allow for 
sufficient airflow and ease in servicing.
Installation
Read these instructions in their entirety before you begin. Locate the shipping carton, remove 
the rack-mounting kit, and prepare to work with it. 
The rack-mounting kit contains two rail assemblies. Each assembly consists of two sections: 
•     
An inner fixed chassis rail that secures directly to the ReadyNAS 3100 chassis.
•     
An outer fixed rack rail that secures directly to the rack itself.