Eaton T982A2-F-SL-115 User Manual

Page of 6
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999 
4
Option 2: EMI/RFI Filtering
Choose “N” for no filtering or “F” for filtering. See below for filtering specifications.
Option 3: Receptacle Type
Choose either straight blade or twist lock style receptacles. See the table in Option 1 for a view of the available receptacles. 
Their NEMA designation number refers to the receptacles.
Option 4: Plug Type
Choose either straight blade or twist lock style plug. See the table in Option 1 for a view of the available plug styles. The NEMA designation number 
refers to the plug. Verify you have the correct type of mating receptacle available at your facility. Plug types limit the voltage and current options. 
Option 5: Current Meter
This unit is available with or without a front panel digital current reference meter. This two-segment current reference meter will 
display the current value of the connected load. (The meter is an AC averaging meter.) This allows you to properly load your 
Power Distribution Unit to avoid an overload situation. This can also be used for monitoring to detect a fault before it occurs. 
The display shows two digits with no decimal place. The meter is accurate to +/- 1 amp resolution. 
The current meter option is 
not available on the following versions: G1 and J1.
Option 6: Power Cable Length
The power distribution unit has either SO, SOOW or SJT type power cable. The length can be specified as 9 feet or 15 feet. 
The maximum length allowed by UL standards for an attached power cable is 15 feet. For permanent installations exceeding 15 feet, 
a licensed electrician should install a permanent circuit. 
EMI/RFI FILTERING COMMON MODE INSERTION LOSS
Mhz.
.15
.50
1.0
5.0
10.0
30.0
dB.
6
19
28
42
45
50
DIFFERENTIAL INSERTION LOSS
Mhz.
.15
.50
1.0
5.0
10.0
30.0
dB.
2
40
60
65
57
55
Environmental
Operating Temperature is 0 to 50 C
Storage Temperature is -40 to 70 C
Altitude Maximum 10,000 ft.
Relative Humidity is 95% Max Non-Condensing
EMI/RFI FILTERING COMMON MODE INSERTION LOSS
Mhz.
.15
.50
1.0
5.0
10.0
30.0
dB.
6
19
28
42
45
50
DIFFERENTIAL INSERTION LOSS
Mhz.
.15
.50
1.0
5.0
10.0
30.0
dB.
6
6
30
50
30
30
15A & 20A Models
30A Models