CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
1
APC InfraStruXure for Small Data Centers, 20kW Base Building Block
GUIDE SPECIFICATIONS FOR
10kW-20kW UPS/Distribution
PART 1 - GENERAL
1.1
SUMMARY
A.
This specification describes the operation and functionality of a continuous duty, three-
phase, solid-state, static Uninterruptible Power System (UPS) hereafter referred to as
the UPS. The UPS shall utilize an N+1 redundant, scalable array architecture. The
system power train shall be comprised of hot swappable / user replaceable
10kW/10kVA power modules, which shall operate in parallel, and be configured for
N+1 redundant operation at rated load. Each 10kVA/10kW power module contains a
full rated input rectifier / boost converter (hereafter referred to as Input Converter), full
rated output inverter, and 10% battery charging circuit. The system shall also comprise
of a user-replaceable continuous duty bypass static switch module, hot swappable / user
replaceable battery modules, redundant control modules, redundant logic power
supplies, and LCD interface display. System static switch shall be capable of being fed
from the same input as the rectifier or a separate input. All of the above system
components are housed in two standard, 24 inch wide, 36 inch deep, 42U high
equipment racks.
phase, solid-state, static Uninterruptible Power System (UPS) hereafter referred to as
the UPS. The UPS shall utilize an N+1 redundant, scalable array architecture. The
system power train shall be comprised of hot swappable / user replaceable
10kW/10kVA power modules, which shall operate in parallel, and be configured for
N+1 redundant operation at rated load. Each 10kVA/10kW power module contains a
full rated input rectifier / boost converter (hereafter referred to as Input Converter), full
rated output inverter, and 10% battery charging circuit. The system shall also comprise
of a user-replaceable continuous duty bypass static switch module, hot swappable / user
replaceable battery modules, redundant control modules, redundant logic power
supplies, and LCD interface display. System static switch shall be capable of being fed
from the same input as the rectifier or a separate input. All of the above system
components are housed in two standard, 24 inch wide, 36 inch deep, 42U high
equipment racks.
B.
In addition, this specification describes the performance, functionality, and design of
the UPS Maintenance Bypass Cabinet and power distribution section of the UPS. In
addition this specification also includes multi-conductor overhead distribution, rack
level power management products, the Battery System, and connectivity solutions
including complete InfraStruXure
the UPS Maintenance Bypass Cabinet and power distribution section of the UPS. In
addition this specification also includes multi-conductor overhead distribution, rack
level power management products, the Battery System, and connectivity solutions
including complete InfraStruXure
TM
system management solutions.
C.
The UPS and associated equipment shall operate in conjunction with a primary power
supply and an output distribution section to provide quality uninterrupted power and
distribution for mission critical, electronic equipment load. The entire system shall bear
the UL60950 listing as a complete product solution.
supply and an output distribution section to provide quality uninterrupted power and
distribution for mission critical, electronic equipment load. The entire system shall bear
the UL60950 listing as a complete product solution.
D.
All programming and miscellaneous components for a fully operational system as
described in this specification shall be available as part of the System.
described in this specification shall be available as part of the System.
1.2
STANDARDS
A.
UL 1778
Uninterruptible Power Supply Equipment
B.
UL60950 Information
Technology
Equipment