Honeywell Liquid Cooled 45kW Home Standby Generator Owner's Manual

Page of 80
WEATHER AND MAINTENANCE KITS
To keep the generator running at its peak, the following kits are 
offered:
•  Cold Weather Kit
~ Recommended for climates with temperatures below 32° F.
•  Scheduled Maintenance Kit
~  Kit includes the recommended parts to maintain the genera-
tor. Refer to the Service Schedule for regular maintenance 
intervals.
For additional information, or to order any of these kits, please 
contact an Authorized Service Dealer or Customer Service 
Representative.
RECONFIGURING THE FUEL 
SYSTEM
NOTE:
All models are configured to run on natural gas from the fac-
tory.
Before the generator can be operated using a LP fuel source, the 
fuel system and control panel (refer to the installation drawing for 
location) must be reconfigured. The steps to reconfigure the gen-
erator from a natural gas (NG) to a liquidified petroleum (LP) fuel 
source are as follows:
FUEL SYSTEM
1.  Turn the main gas supply off and disconnect the battery.
2.  Remove the carburetor fuel hose from the outlet port of the 
demand regulator (see Figure 6.1).
3.  Disconnect the power wires from the fuel solenoid located 
on top of the regulator assembly by removing the screw on 
the front of the connector and pulling the connector forward, 
away from the solenoid body.
4.  Loosen the spring clamp on the small fuel enrichment line and 
remove the hose from the hose barb.
5.  Remove the black pipe assembly from the outlet port of the 
demand regulator. The solenoid assembly may need to be 
removed before performing this operation (Figure 6.1).
6.  Remove the NG fuel jet (loosen counter clockwise) from the 
outlet port. 
7.  Remove the LP fuel jet (loosen counter clockwise) from the jet 
keeper port on the side of the regulator housing. Install this jet 
into the outlet port in the regulator casting.
NOTE:
The jet sizes are stamped on the individual jets. The larger jet 
size is used for running on NG.
8.  Install the previously removed NG jet into the jet keeper port 
on the side of the regulator housing. 
9.  Install the previously removed black pipe onto the outlet 
port of the demand regulator. Use pipe sealant on the pipe 
threads.
10.  Reverse steps 1-4 in this procedure to reactivate the demand 
regulator.
11.  Follow the instructions in the Control Panel section.
 
 Serious injury, including death, or damage 
may occur if not configured properly. Please 
consult an Authorized Dealer with any ques-
tions.
Figure 6.1 — Reconfigure the Fuel System
CONTROL PANEL
The FUEL TYPE must be reconfigured in the control panel to final-
ize the conversion process. This generator is configured at the 
factory to operate on natural gas. If conversion to LP is required, 
please complete the mechanical conversion process and then call 
888-9ACTIVATE for the control panel password. This fuel selection 
conversion is required to be password protected by Environmental 
Protection Agency [EPA] regulations. 
 
 Whenever the Generator’s Fuel Regulator is 
converted from one Fuel type to the other, 
the Control Panel must be reconfigured for 
the correct fuel type. Failure to convert both 
the Regulator and Control Panel will result in 
decreased performance and an increase in 
emissions, and is a violation of EPA regula-
tions.
6-2
GenSpec094  Rev
. B  05/11