Honeywell Thermostatic Mixing Valve Product Datasheet

Page of 12
AM-1 1070 SERIES PROPORTIONAL THERMOSTATIC MIXING VALVE
3
62-3114EF—01
ASSE 1070 Applications:
These AM-1 1070 models can be installed in any position 
consistent with the intended use. The AM-1 1070 shall be 
installed as shown in Fig. 1 or 2. Check valves, as indicated, 
may be installed to prevent migration of hot water into the cold 
branch and cold water into the hot branch through the AM-1 
1070 Valve. Sweat union connections (if used) should be 
soldered prior to assembly to the valve or without the sealing 
gasket or optional plastic check valve present. After the joint 
has cooled, the sealing gasket and / or check valves may be 
installed.
Fig. 2. AM Series ASSE 1070 - Two Handle Fixtures.
Fig. 3. AM Series ASSE 1070 - Handleless Fixtures.
Domestic Water Mixing (Tempering)
(ASSE 1017) (Source of Hot Water)
Use when water temperature produced by heater is hotter than 
designed at point of use. Many codes require that water 
supplied to the system be limited to 120° F (49° C) max.
Fig. 4. Water Heater Without Recirculation.
Fig. 5. Water Heater With Recirculation.
SYMBOLS
1 = Check Valve/Flow Check
V = Any device which turns the domestic water system into 
a closed system such as; backflow preventers, check 
valves or pressure reducing valves.
T= Honeywell Aquastat
WATER
HEATER
HOT 
WATER
SUPPLY
COLD WATER
SUPPLY
TEMPERED
TO FIXTURE COLD
(1)
M  (1)
H
C
AM SERIES
TEMPERED
TO FIXTURE
(1)
M  (1)
H
C
AM SERIES
COLD
NOTE:  (1) = CHECK VALVES
M23939
WATER
HEATER
HOT 
WATER
SUPPLY
COLD WATER
SUPPLY
TEMPERED
TO FIXTURE
(1)
M  (1)
H
C
AM SERIES
TEMPERED
TO FIXTURE
(1)
M  (1)
H
C
AM SERIES
M23940
OPTIONAL
RECIRCULATION
SYSTEM
M25410
HEAT TRAP
6“
8“ MAX
WATER
HEATER
EXPANSION
TANK
ALLOWABLE
SERVICE
VALVE
LOCATION
AM SERIES
WATER USE FIXTURES
M
COLD WATER
SUPPLY
C
V
H
TO DISHWASHER IF
PERMITTED BY CODES
CHECK VALVE
M25029
(1)
T
(1)
HEAT TRAP
6“
8“ MAX
WATER
HEATER
EXPANSION
TANK
ALLOWABLE
SERVICE
VALVE
LOCATION
AM SERIES
WATER USE FIXTURES
RECIRCULATION
PUMP
M
COLD WATER
SUPPLY
C
V
H
TO DISHWASHER IF