Cisco Prisma II 1310 nm HDTx Transmitters Installation Guide

Page of 125
2-16 
Installation 
78-4010846-01 Rev D 
External Alarms Connections,
 Continued 
Master/Slave Illustration 
 
Prisma II Redundancy Interface Panel 
The Prisma II Redundancy Interface Panel is an accessory to the Prisma II platform.  
It is intended to be used with the master/slave feature and the contact closure alarm 
feature of the Prisma II platform. 
The Prisma II Redundancy Interface Panel serves as an extension to the two DB-37 
connectors labeled ALARM IN and ALARM OUT on the connector interface panel 
of the Prisma II Chassis. The terminals on the redundancy interface panel are 
extensions of pins on the ALARMS OUT and ALARMS IN connectors on the 
Prisma II Chassis.   
Refer the section titled The Prisma II Redundancy Interface Panel in Chapter 2 of 
the Prisma II Chassis Installation and Operation Guide, part number 713375. 
 
 
Inter-module connections are made on
the back of the chassis using
"ALARMS IN" and "ALARMS OUT"
connectors.
SLAVE MODULE
MASTER MODULE
ENABLE
CONTROL
ALARM
RELAY
ALARM
RELAY
MASTER/
SLAVE
CONTROL
MASTER/
SLAVE
CONTROL
M
S
M
S
To make a module a MASTER, set the
Master/Slave control to "Master" (the default).
The state of the slave input is ignored.
To make a module a SLAVE, set the
Master/Slave control to "Slave". The slave
will not turn on unless the master module
is removed or has a critical fault.
NORMAL
CRITICAL FAULT
CRITICAL FAULT
NORMAL
ENABLE
CONTROL
A high
enables the
module (e.g.
turns on the
module)
A high
enables the
module (e.g.
turns on the
module)
OFF
ON
OFF
ON
Part of
ALARMS IN
connector
Part of
ALARMS IN
connector
Part of
ALARMS OUT
connector
Part of
ALARMS OUT
connector