Cisco Cisco Nexus 7000 4-Slot Switch Troubleshooting Guide

possibly due to On/Off or power cable removal/
2013 Oct 17 17:06:40 ... last message repeated 14 times
Root Cause
This issue is due to either a faulty or disconnected power cable, or a power supply failure.
Solution
Check the output of the show env power detail command and research the power supply status. In this
example output, both chords are connected but the second shows only 1200W capacity instead of 3000W and
it needs to be for the 220V AC on the N7K−AC−6.0KW. The power source tested OK. Replace the power
supply.
example output, both chords are connected but the second shows only 1200W capacity instead of 3000W and
it needs to be for the 220V AC on the N7K−AC−6.0KW. The power source tested OK. Replace the power
supply.
PS_2 total capacity: 4200 W Voltage:50Vchord 1 capacity: 3000 W chord 1
connected to 110v AC chord 2 capacity: 1200 W chord 2 connected to 220v AC
Problem: %PLATFORM−5−PS_STATUS: PowerSupply X
PS_FAIL Alarm
PS_FAIL Alarm
This alert appears on the platform:
%PLATFORM−5−PS_STATUS: PowerSupply 3 current−status is PS_FAIL
%PLATFORM−2−PS_FAIL: Power supply 3 failed or shut down (Serial number xxxxx)
Root Cause
This alert is due to either a faulty or disconnected power cable, or a power supply failure.
Solution
Check the output of these commands:
show environment power detail
♦
show power
♦
1.
Reseat the failed power supply. Use the redundant power supply in order to ensure the power does not
go offline.
go offline.
2.
Submit a RMA for the power supply. Use the redundant power supply in order to ensure the power
does not go offline.
does not go offline.
3.
References
Cisco Nexus 7000 Series Power Supply Redundancy
Problem: Power Supply Issue on FEX
These alarms appear for the FEX power supply:
%SATCTRL−FEX104−2−SOHMS_DIAG_ERROR: FEX−104 Module 1: Runtime diag detected major event:
Voltage failure on power supply: 1
%SATCTRL−FEX104−2−SOHMS_DIAG_ERROR: FEX−104 System minor alarm on power