Cisco Cisco CRS-X Multishelf System Installation Guide

Page of 60
Before you begin this procedure, ensure that all power is disconnected from the Cisco CRS PDU. Remove
the PDU input plug(s) from the branch circuit outlet(s).
Caution
Before you install the PDU, be aware of the following:
• Consideration should be given to the connection of the equipment to the supply circuit, and to the effect that overloading of the
circuits might have on overcurrent protection and supply wiring. Appropriate consideration of equipment nameplate ratings
should be used when addressing this concern.
• Particular attention should be given to supply connections other than direct connections to the branch circuit (for example, use
of power strips).
Although there are differences between the left and right chassis mounting brackets, the PDUs are installed
on the left and right sides of the Cisco CRS 16-slot line card chassis using the same procedures.
Note
Required Tools and Equipment
The following tools are required to install the PDU on the Cisco CRS 16-slot line card chassis:
• Number 1 x 6 in. Phillips screwdriver
• M12 6pt. combination wrench
• Torque wrench with M12 6pt. socket and rated accuracy at 40 to 50 in-lb (4.52 to 5.65 N-m)
• PDU
◦AC Delta PDU kit (Cisco product number CRS-16-PDU-Delta=), or
◦AC Wye PDU kit (Cisco product number CRS-16-PDU-Wye=)
Steps
To install the PDU on the side of the chassis, perform the following steps:
Procedure
Step 1
Using the number 1 Phillips screwdriver, loosen the four flat head screws that attach each rack mounting bracket to the
left and right side of the PDU.
Step 2
Remove the rack mounting brackets and screws and set them aside.
Step 3
Slide the PDU into the chassis mounting bracket. Align the screw holes on the PDU with the screw holes on the top of the
chassis mounting bracket. See the below figure.
35