Cisco Cisco ONS 15454 M2 Multiservice Transport Platform (MSTP)

Page of 23
• Coding-Choose the coding used by your BITS reference, either B8ZS (binary 8-zero substitution) or AMI (alternate
mark inversion).
• Framing-Choose the framing used by your BITS reference, either ESF (Extended Super Frame) or SF (D4) (Super
Frame).
• Sync Messaging-Check this check box to enable SSM. SSM is not available if Framing is set to Super Frame.
• Admin SSM-If the Sync Messaging check box is not checked, you can choose the SSM Generation 2 type from the
drop-down list. Choices are PRS (Primary reference source; Stratum 1), ST2 (Stratum 2), TNC (Transit Node Clock),
ST3E (Stratum 3E), ST3 (Stratum 3), SMC (SONET minimum clock), and ST4 (Stratum 4).
Step 8
In the BITS Out area, complete the following information, as needed:
• Facility Type-(TCC2P/TNC/TNCE/TSC/TSCE only) Choose the BITS Out signal type, either DS1 or 64KHz+8KHz
for ANSI and E1, 2Mhz, or 64Khz for ETSI.
• BITS Out state-If equipment is connected to the node's BITS output pins on the backplane (ANSI) or MIC-C/T/P
FMEC (ETSI) and you want to time the equipment from a node reference, set the BITS Out state for BITS-1, BITS-2,
or both, to IS , depending on which BITS Out pins are used for the external equipment. If equipment is not attached
to the BITS output pins, set the BITS Out state to OOS .
Step 9
If the BITS Out state is set to OOS, continue with
If the BITS Out state is set
to IS, complete the following information:
• Coding-Choose the coding used by your BITS reference, either B8ZS, AMI, or HDB3.
• Framing-Choose the framing used by your BITS reference, either ESF, SF (D4), or FAS+CAS+CRC.
• AIS Threshold-If SSM is disabled or Super Frame is used, choose the quality level where a node sends an alarm
indication signal (AIS) from the BITS 1 Out and BITS 2 Out backplane pins (ANSI) or MIC-C/T/P FMEC (ETSI).
An AIS alarm is raised when the optical source for the BITS reference falls to or below the SSM quality level defined
in this field.
• LBO-If an external device is connected to the BITS Out pins, set the line build-out (LBO) distance between the ONS
15454 and an external device. If an external device is connected to BITS Out, choose the distance between the device
and the ONS 15454 . Options are: 0-133 ft (default), 134-266 ft, 267-399 ft, 400-533 ft, and 534-655 ft. Line build
out (LBO) relates to the BITS cable length. If an external device is not connected to BITS Out, leave this field set
to the default.
Step 10
Click Apply.
Refer to Cisco ONS 15454 DWDM Troubleshooting Guide for timing-related alarms.
Note
Step 11
Return to your originating procedure (NTP).
DLP-G96 Set Up Internal Timing
This task sets up internal timing (Stratum 3) for an ONS 15454
.
Purpose
None
Tools/Equipment
9