MegaRAID SAS Controller Replacement Procedure 
OL-27138-01 
 
 
 
All contents are Copyright © 2012 Cisco Systems, Inc. All rights reserved. Important Notices and Privacy Statement.
 
36 
 
 
Figure 39: New MegaRAID controller 
 
10.  Install the new MegaRAID controller card into slot 3 
– ensuring it is fully seated into the 
PCIe slot;  
11.  Re-attach slot screw to firmly attach new SAS controller into slot 3, and check that all 
slots screws are tightened. 
12.  Replace the top cover and put the chassis back. 
13.  Replace the power supplies and reconnect all cables, make sure you verify labels after all 
cables and fiber/copper are connected to interface.    
4.  Importing the Logical Drive Configuration 
After replacing the MegaRAID controller physically, the existing logical drive configuration on 
this server is no longer on the new MegaRAID controller but it still exists on the physical 
internal drives. So, we need to import the configuration from the internal drive to the new 
MegaRAID controller. This can be done when initializing the new MegaRAID controller during 
the first booting up after replacing the controller if prompted. 
 
1.  Power up the server. During the first time after replacing the MegaRAID controller, if the 
following message
s ” Memory/battery problems were detected” and “The adapter has 
recovered, but cached data was lost” are seen as in the below figure, then press any key 
to continue. Other messages could be displayed on the local RGB monitor shown in 
Figure 40. The console will then pause waiting for operator input: