Cisco Model D-PCG1000 PowerKEY CAS Gateway Installation Guide

Page of 136
 
Chapter 5    Troubleshooting the GQAM 
 
 
 
100 
4014102 Rev C 
LCD 
Description 
Alarm 
Level 
Probable Cause 
Check and Correct 
RF (1-4) DC 
Lock detect 
error 
See also RF (1-
4) UC Lock 
detect error 
Major 
 
Downconverter (DC) lock 
detect signal not functioning 
correctly. During Modulator 
MCU Power On Self Test 
(POST), the lock detect signal 
from the downconverter phase-
locked loop (PLL) did not 
indicate an unlocked condition 
when one existed 
Note: Since the MCU cannot 
correctly detect locked or 
unlocked status, the RF Output 
field displays “MUTED” when 
this condition occurred 
 
The output converter 
synthesizer lock detect circuitry 
has malfunctioned 
Contact Cisco Services 
RF (1-4) DC 
PLL unlocked 
Major  Downconverter (DC) PLL 
synthesizer cannot lock. The output 
frequency may not be correct. The 
RF Output field displays “MUTED” 
when this condition exists 
Contact Cisco Services 
RF (1-4) 
EEPROM 
failure 
Minor  Modulator EEPROM failure. The 
EEPROM on the modulator board is 
not present or is not operational. If 
this alarm is set, RF calibration data 
is not available and the “RF (1-4) 
Level not calibrated” alarm is also 
active 
Contact Cisco Services 
RF (1-4) 
Exceeded max 
temp 
Minor  The internal temperature of the 
GQAM is more than 70ºC (158ºF) 
 
Remove vent obstructions 
 
Provide more cooling and 
ventilation 
 
Check the exhaust fans 
 
Contact Cisco Services 
Important! You should 
check the temperature on 
the GQAM daily or more 
frequently if possible. 
RF (1-4) level 
not calibrated 
Minor  One of the RF Level settings is not 
calibrated to the correct frequency 
or the EEPROM that stores the 
calibration data is not operational 
Contact Cisco Services