Cisco Model GS7000 4-Port Node 1 GHz with 42 54 Split Installation Guide

Page of 76
 
Chapter 4    Troubleshooting
 
34 
4024769 Rev A
Improper Configuration of the LCM 
An improperly configured LCM can be the cause of this indication.  Improperly 
configured, for example, can mean that the LCM's configuration does not match the 
actual receivers/transmitters mounted in the node.  This could happen if the LCM 
you are using was previously used in another node. 
Complete the following steps to troubleshoot. 
1  Verify the LCM configuration.  Refer to Configuring the LCM (on page 22) for 
instructions on properly configuring the LCM. 
2  If the LCM configuration is correct, then follow the procedures in the next 
section to check for an operating condition that could cause the alarm. 
 
  
WARNING: 
The Model GS7000 Node's forward segmentation is set at the factory to match 
the installed Forward Configuration Module (FCM).  A mismatch between the 
forward segmentation and the FCM may cause isolation or loss of service.
 
 
Real Operating Condition Problems 
Complete the following steps to determine what operating condition alarms exist. 
1  Connect the Model 91200 Handheld Programming Terminal to the local control 
port on the LCM.  Refer to Configuring the LCM Using the Model 91200 
Handheld Programming Terminal for instructions. 
2  Use menu item 1 - RX & TX Config to check which receivers and transmitters 
are set as Present or Absent in the node.  The configuration settings must match 
what is physically installed and operating. 
3  Use menu item 2 - PS Config to check which AC lines and PS modules are set as 
Present or Absent in the node.  The configuration settings must match what is 
physically installed. 
4  Use menu item 3 - RX Thresholds to check the RX threshold levels.  Are they 
correct?  If not, reset the values. 
5  Use menu item 4 - TX Thresholds to check the TX threshold levels.  Are they 
correct?  If not, reset the values. 
6  Use menu item 6 - Rx & Tx Power to check the operating power levels against 
set threshold levels for alarms from steps 4 and 5. 
7  Use menu item 7 - Power Supplies to check the power supply measurements for 
out-of-range values. 
Note:  The thresholds for the power measurements are neither shown nor 
settable via the handheld terminal.  These thresholds are hard-coded.