Cisco Prisma II 1310 nm HDTx Transmitters Installation Guide

Page of 142
 
 
External Alarms Connections 
78-4009700-01 Rev E 
31 
 
External Alarms Connections 
Master/Slave Operation 
All Prisma II modules ship from the factory configured as a master. The LCI, TNCS 
software, or the ICIM can be used to reconfigure a module as a slave or as 
redundant. The Prisma II Chassis allows for local hard-wired redundancy by using 
the ALARM IN and ALARM OUT connectors located on the connector interface 
panel. A pair of modules can be configured so that if the master fails, the slave takes 
over by using the ALARM IN and ALARM OUT connectors. 
 
ALARMS IN and ALARMS OUT Connectors 
Every Prisma II Standard and II XD chassis provides connectors for external alarms 
to and from each module slot. These alarm connectors are located on the chassis 
connector panel and are labeled ALARMS IN and ALARMS OUT
For detailed information on ALARM IN and ALARM OUT connectors, see the 
Prisma II Chassis Installation and Operation Guide, part number 713375 or the Prisma 
II™ XD Platform System Guide, part number 4021339. 
When a critical alarm occurs in a Master module, the Master turns off and the Slave 
(redundant module) is enabled. To make this happen, the pin representing the 
Master module slot in the ALARM OUT connector must be externally wired to the 
pin representing the Slave module slot in the ALARM IN connector. After wiring 
these contacts, take care to ensure that the Master and Slave modules are not moved 
to other slots. Otherwise, the ALARM IN and ALARM OUT connectors will need to 
be rewired to the appropriate pins. 
Note: 
 
Any device configured as Single or Master ignores its ALARM IN contacts. 
 
To verify proper wiring and redundant configuration, simply unplug the Master 
module and observe that the Slave module turns on.