Moxa ICF-1150I-M-SC-T User Manual

Page of 3
1
w w w. m o x a . c o m
i n f o @ m o x a . c o m
Serial Media Converters
Pull High/Low Resistor Values
Position
0
1
2
3
4
5
6
7
8
9
ohms
150K
10K
4.7K
3.3K
1K
909
822
770
500
485
ICF-1150 Series
RS-232, fiber, and RS-422/485 3-way communication
 
Rotary switch to change the pull high/low resistor value
 
Extend RS-232/422/485 transmission up to:
 
40 km with single-mode
  
·
5 km with multi-mode
  
·
3-way Galvanic Isolation (for “I” model only)
 
-40 to 85°C wide temperature models available
 
Class I, Div. II certification
 
The ICF-1150 series support 2 serial ports, with a D-sub connector for 
RS-232 communication and a removable terminal block for RS-422 or 
RS-485 communication. The 3 ports (2 serial ports and one fiber port) 
are completely independent. When an ICF-1150 converter receives data 
from any one port, it will send the data out through the other 2 ports. 
For example, once the ICF-1150 converter receives a command from 
The RS-485 interface supports multi-drop or daisy-chain connections, 
which system engineers will use to connect serial devices such as 
meters, RTUs, and readers together on the same bus. Since the 
number of serial devices on the same bus will cause the impedance 
the remote master through the fiber port, it will convert the signal and 
send the command through the RS-232 and RS-422/485 ports at the 
same time. If the user is monitoring a system running on an RS-485 
network, there is no need to use an additional RS-232 to RS-485 
converter to connect the laptop computer’s serial port to the RS-485 
bus.
of the data line to increase, the ICF-1150 allows users to tune the 
pull high/low resistor. Just rotate the switch to the appropriate value 
without removing the ICF-1150 from the DIN-rail.
Three-Way Communication
Rotary Switch for Setting the Pull High/Low Resistor
Specifications
Industrial serial-to-fiber converters
Optical Fiber Side
Fiber Connector: SC or ST
Cable Requirements: 
Single-mode: 8.3/125, 8.7/125, 9/125, or 10/125 μm 
Multi-mode: 50/125, 62.5/125, or 100/140 μm
Transmission Distance: 
Single-mode: 40 km 
Multi-mode: 5 km
Wavelength: 
ICF-1150-S (single-mode): 1310 nm 
ICF-1150-M (multi-mode): 850 nm
Tx Output: 
ICF-1150-S (single-mode): > -5 dBm 
ICF-1150-M (multi-mode): > -5 dBm
Rx Sensitivity: 
ICF-1150-S (single-mode): -25 dBm 
ICF-1150-M (multi-mode): -20 dBm
Point-to-Point Transmission: Half-duplex or full-duplex
Multi-drop Transmission: Half-duplex, fiber ring
RS-232/422/485 Side
RS-232 Signals: TxD, RxD, GND
RS-422 Signals: TxD+, TxD-, RxD+, RxD-, GND
RS-485-4w Signals: TxD+, TxD-, RxD+, RxD-, GND
RS-485-2w Signals: Data+, Data-, GND
Baudrate: 50 bps to 921.6 Kbps
ESD Protection: 15 KV for all signals
Isolation: 2 KV RMS isolation per I/O port for 1 minute