Moxa PT-7828-R-48-HV User Manual

Page of 6
2
w w w. m o x a . c o m
i n f o @ m o x a . c o m
Industry-specific Ethernet Switches
440.0 mm (17.3 in)
457.0 mm (18.0 in)
44.0 mm
(1.7 in)
462.6 mm (18.2 in)
480.0 mm (18.9 in)
349.3 mm (13.8 in)
31.8 mm
(1.3 in)
325.0 mm (12.8 in)
Rear View
Top View
Front View
Side View
Protocols: IGMPv1/v2, GMRP, GVRP, SNMPv1/v2c/v3, DHCP Server/
Client, BootP, TFTP, SNTP, SMTP, RARP, RMON, RIP V1/V2, HTTP, 
HTTPS, Telnet, SSH, Syslog, DHCP Option 66/67/82, LLDP, Modbus/
TCP, IEEE 1588 PTP, SNMP Inform
Layer 3 Switching: Static routing, RIP V1/V2, OSPF, VRRP for router 
redundancy
MIB: MIB-II, Ethernet-like MIB, P-BRIDGE MIB, Q-BRIDGE MIB, Bridge 
MIB, RSTP MIB, RMON MIB Groups 1, 2, 3, 9
Flow Control: IEEE 802.3x flow control, back pressure flow control 
Switch Properties
Priority Queues: 4
Max. Number of Available VLANs: 64
VLAN ID Range: VID 1 to 4094
IGMP Groups: 256
Interface 
Fast Ethernet: Slots 1, 2, and 3 for combinations of 4, 6, 7, or 8-port 
PM-7200 fast Ethernet modules with 10/100BaseT(X) (TP/M12 
interface), 100BaseFX (SC/ST connector), or 100BaseSFP.
Gigabit Ethernet: Slot 4 for 2 or 4-port PM-7200 Gigabit Ethernet 
combo module, 10/100/1000BaseT(X) or 1000BaseSFP
Console Port: RS-232 (RJ45)
System LED Indicators: STAT, PWR1, PWR2, FAULT, MSTR/HEAD, 
CPLR/TAIL
Mode LED Indicators: LNK/ACT, FDX/HDX, RING PORT, COUPLER 
PORT, SPEED
Alarm Contact: 1 relay output with current carrying capacity of 3 A @ 
30 VDC or 3 A @ 240 VAC
Power Requirements
Input Voltage:  
• 24 VDC (18 to 36 V) 
• 48 VDC (36 to 72 V) 
• 110/220 VDC/VAC (88 to 300 VDC, 85 to 264 VAC)
Input Current: (all ports are equipped with fiber) 
• Max. 2.58 A @ 24 VDC 
• Max. 1.21 A @ 48 VDC  
• Max. 0.64/0.33 A @ 110/220 VDC 
• Max. 0.53/0.28 A @ 110/220 VAC
Overload Current Protection: Present
Connection: 10-pin terminal blocks 
Reverse Polarity Protection: Present 
Physical Characteristics  
Housing: IP30 protection
Dimensions: 440 x 44 x 325 mm (17.32 x 1.73 x 12.80)
Weight: 5900 g
Installation: 19’’ rack mounting
Environmental Limits
Operating Temperature: -40 to 85°C (-40 to 185°F), cold start requires 
min. of 100 VAC at -40°C
Storage Temperature: -40 to 85°C (-40 to 185°F) 
Ambient Relative Humidity: 5 to 95% (non-condensing) 
Regulatory Approvals 
Safety: UL60950-1, CSA C22.2 No. 60950-1, EN60950-1
EMI: FCC Part 15, CISPR (EN55022) class A
Power Automation: IEC 61850-3, IEEE 1613
Traffic Control: NEMA TS2
Rail Traffic: EN50155, EN50121-4
Note: Please check Moxa’s website for the most up-to-date certification status.
Warranty
Warranty Period: 5 years
Details: See www.moxa.com/warranty
Dimensions