Omron C200HW-CLK21 User Manual

Page of 401
230
Response Codes
Section 6-7
20: Read not possible
02
The data is protected.
Execute the instruction again after issuing 
the PROGRAM AREA PROTECT CLEAR 
command to the PLC.
An attempt was made to download a 
file that is being uploaded.
Check the file name and either interrupt ser-
vicing or wait for servicing to complete 
before re-executing the command.
03
The registered table does not exist or is 
incorrect.
Set or reset the registered table.
Too many files open.
Close open files and re-execute the com-
mand.
04
The corresponding search data does 
not exist.
---
05
A non-existing program no. has been 
specified.
Check the program number and be sure 
that it is set correctly.
06
A non-existing file has been specified.
Check whether the correct file name was 
used.
07
A verification error has occurred.
Check whether the memory contents are 
correct and replace if incorrect.
Check the contents of the file. A read error 
may have occurred.
21: Write not possible
01
The specified area is read-only or is 
write-protected.
If the specified area is read-only, the write 
cannot be performed. If it is write-protected, 
turn off the write-protect switch and execute 
the instruction again.
02
The data is protected.
Execute the instruction again after issuing 
the PROGRAM AREA PROTECT CLEAR 
command to the PLC.
An attempt was made to simulta-
neously download and upload a file.
Check the file name and either interrupt ser-
vicing or wait for servicing to complete 
before re-executing the command.
The data link tables cannot be written 
manual because the Unit is set for 
automatic generation.
Change the data link mode to manual.
03
The number of files exceeds the maxi-
mum permissible.
Write the file(s) again after erasing 
unneeded files, or use different disk or 
Memory Card that has free space.
Too many files open.
Close open files and re-execute the com-
mand.
05
A non-existing program no. has been 
specified.
Check the program number and be sure 
that it is set correctly.
06
A non-existent file has been specified.
Check the file name and execute again.
07
The specified file already exists.
Change the name of the file and execute 
the instruction again.
08
Data cannot be changed.
---
Main code
Sub-
code
Probable cause
Remedy