1.1
Power Buses
Each
 fuse panel has two separate power buses (feeds). Each bus distributes the input power to
the
 output power circuits. In each bus circuit, current flows from the input power bus, through
the
 fuse, to the output power circuit. A typical fuse panel block diagram is shown in 
.
The
 current capacity of each bus of the traditional power fuse panel is 65 Amps maximum. The
output
 fusing of the traditional fuse panel should not exceed 65 Amps per bus. This provides a
total
  capacity of 130 Amps  per  panel.  The maximum current per bus is marked on the  fuse
panel.
 
The
 current capacity of each bus of the uninterrupted power fuse panel is 60 Amps maximum.
However,
 the output fusing of the uninterrupted fuse panel should not exceed 30 Amps per bus.
This
 provides a total capacity of 60 Amps per panel. The maximum current per bus is marked
on
 the fuse panel.
Each
 of the feed buses has a capacity of eight fuse positions. Other fuse capacity configurations
may
 be available by special order. When a fuse fails, the input power bus is disconnected from
the
 corresponding output circuit. This causes the alarm LED for the bus to light and also opens
or
 closes the alarm relay contacts (form C contacts). 
1.2
Redundant Power (Uninterrupted Power Fuse Panel)
The
 uninterrupted power fuse panel provides redundant power to fused equipment through the
use
 of Schottky steering diodes. When power to one bus is interrupted, the Schottky steering
diodes
  enable the  other bus to supply power to the entire  fuse panel and to maintain  output
power
 for both buses (bus A and bus B). If bus A loses power, bus B will support the power load
of
 bus A while maintaining its original power load. Likewise, if bus B loses power, bus A will
support
 the power load of bus B while maintaining its original power load.
1.3
Input Voltage
The
 fuse panel can accommodate either –24 Vdc on both buses or –48 Vdc on both buses. The
voltage
 level is sensed by the fuse panel circuitry. The input voltage used with the fuse panel can
have
 the following characteristics:
• –24
 Vdc nominal, within range of –21 Vdc to –30 Vdc
• –48
 Vdc nominal, within range of –42 Vdc to –56 Vdc
Fuse
 panels for use with other input voltage and polarity power may be available by special
order.