HP C7000 User Manual

Page of 71
 
Specifications 65 
Specifications 
Environmental specifications 
 
Specification Value 
Temperature range*
 
 
Operating 10
°
C to 35
°
C (50
°
F to 95
°
F) 
Non-operating -30
°
C to 60
°
C (-22
°
F to 140
°
F) 
Wet bulb temperature 
 
Operating 28ºC 
(82.4ºF) 
Non-operating 
38.7ºC (101.7ºF) 
Relative humidity 
(noncondensing)**
 
 
Operating 20% 
to 
80% 
Non-operating 
5% to 95% 
 
* All temperature ratings shown are for sea level. An altitude derating of 1°C per 304.8 m (1.8°F per 1000 ft) to 
3048 m (10,000 ft) is applicable. No direct sunlight allowed. Upper operating limit is 3,048 m (10,000 ft) or 70 
Kpa/10.1 psia. Upper non-operating limit is 9,144 m (30,000 ft) or 30.3 KPa/4.4 psia. 
** Storage maximum humidity of 95% is based on a maximum temperature of 45°C (113°F). Altitude maximum for 
storage corresponds to a pressure minimum of 70 KPa. 
 
Enclosure specifications 
 
Specification Value 
Product dimensions 
 
Height 
442.0 mm (17.4 in) 
Depth 
813.0 mm (32.0 in) 
Width 
445.0 mm (17.5 in) 
Shipping dimensions 
 
Height 
759.00 mm (29.88 in) 
Depth 
1013.00 mm (39.88 in) 
Width 
607.00 mm (23.88 in) 
Single-phase enclosure weight * 
 
Unboxed 
54.9 kg (121.0 lb) 
Shipping 
74.4 kg (164.0 lb) 
Three-phase enclosure weight * 
 
Unboxed 
68.0 kg (150.0 lb) 
Shipping 
87.5 kg (193.0 lb)