HP r5500 User Manual

Page of 61
 
Specifications 44 
UPS model 
Utility voltage 
frequency (Hz) 
Available settings utility 
voltage (VAC)  
Dedicated 
branch circuit 
rating (A) 
Line cord 
R5500 XR INTL 
50/60 
200/208, 220, 230*, 
240 
32 
Nondetachable power 
cord with 32 A IEC-309 
plug 
 
 
UPS output specifications 
              
UPS model 
Load 
segment 
Circuit 
breaker 
Output receptacles 
Maximum current 
R5500 XR NA/JPN 
15 A¹ 
2 x IEC-320-C19 
15 A per receptacle² 
 
 
 
2 x IEC-320-C13 
10 A per receptacle 
 
 
 
1 x L6-30R 
Up to full UPS power rating 
 
15 A¹ 
2 x IEC-320-C19 
15 A per receptacle² 
 
 
 
2 x IEC-320-C13 
10 A per receptacle 
R5500 XR INTL 
15 A¹ 
2 x IEC-320-C19 
15 A per receptacle² 
 
 
 
2 x IEC-320-C13 
10 A per receptacle 
 
 
 
1 x IEC-309-32A 
Up to full UPS power rating 
 
15 A¹ 
2 x IEC-320-C19 
15 A per receptacle² 
 
 
 
2 x IEC-320-C13 
10 A per receptacle 
 
¹ 
  NOTE:  The circuit breakers protect the C19 and C13 outlets. 
² 
  NOTE:  If an extension bar is connected to a C19 receptacle, the maximum current for each C13 receptacle 
on the extension bar is 10 A. The total maximum current for the extension bar is 12 A. 
 
Power protection specifications 
     
UPS model 
VA 
Nominal power 
rating (W) 
Nominal voltage 
setting 
R5500 XR NA/JPN 
5000 
4500 
200/208, 220, 
230, 240 
R5500 XR INTL 
6000 
5400 
220, 230, 240 
 
5000 4500 
200/208 
 
 
Voltage specifications 
     
Configuration setting (VAC) 
Available nominal output voltage (VAC) 
200/208 204 
220 220 
230 230 
240 240