Operation 
Modes of Operation 
The UPS has five modes of operation, indicated by the LEDs (see Figure 2-3):  
• 
• 
• 
• 
• 
Standby Mode 
—  When utility is present and output is off, the Utility LED (1) flashes slowly. 
—  Power is not available at the UPS output. 
—  The UPS monitors and charges batteries, if required. 
Operate Mode 
—  The Utility LED (1) is solid green. 
—  The UPS is supplying power to the loads. 
—  The UPS monitors and charges batteries, if required. 
Bypass Mode 
—  The Utility LED (1) and Battery LED (2) are off. 
—  The Bypass LED (3) is solid amber, and an audible alarm is active. 
—  The Alarm LED (4) is solid red. 
—  The utility is bypassing the unit and going directly to the load. 
—  The UPS monitors and charges batteries, if required. 
Battery Mode 
—  The Battery LED (2) is solid amber. 
—  The Alarm LED (4) is solid red. 
—  Utility power is not present. 
—  The UPS does not charge the batteries. 
—  Power is available at UPS outputs. 
Redundant Mode 
—  The Redundant LED (5) is solid green. 
—  At least one electronics module of the load can be in a redundant state (two or more 
electronics modules working). 
—  All electronics modules share the load, but there is enough power to allow an 
electronics module to go out of service. 
2-4 
HP Uninterruptible Power System R12000 XR Models User Guide 
  
 
HP CONFIDENTIAL Codename: Sierra Part Number: 146316-002 Last Saved On: 1/24/03 10:14 AM