Specifications 
HP Uninterruptible Power System R12000 XR Models User Guide 
C-3 
  
 
HP CONFIDENTIAL Codename: Sierra Part Number: 146316-002 Last Saved On: 1/24/03 10:24 AM 
 
Battery Specifications 
 
Table C-4:  Battery Specifications 
Feature Specification 
Type 
Each module contains maintenance-free, sealed, valve 
regulated lead-acid (VRLA) batteries with an eight-year 
minimum float service life at 25
°C (77°F). 
Voltage 
The battery module has a battery string voltage of  
48 Vdc. 
Charging 
Complete charge takes no more than 48 hours.  
 
The UPS recharges in three hours to 80% usable 
capacity.  
ERMs will recharge in less than eight hours to 80% 
usable capacity. 
Battery Runtime 
 
Table C-5:  Estimated Battery Runtime 
Load  
(Percent) 
Estimated Battery 
Runtime (Minutes) 
UPS with ERM  
Runtime (Minutes) 
20 43  69 
50 14  28 
80 7  15 
100 5  11 
Environmental Specifications 
 
Table C-6:  Environmental Specifications 
Feature Specification 
Operating temperature 
10
o
C to 40
o
C (50
o
F to 104
o
F) 
UL-tested at 25
o
C (77
o
F) 
Relative humidity 
0% to 95%; non-condensing 
Operating altitude 
Up to 2,000 m (6,562 ft) above sea level 
Audible noise 
Typically 60 dBA 
Transit temperature 
-25
o
C to +55
o
C (-13
o
F to 131
o
F) 
Transit altitude 
15,000 m (49,212 ft) above sea level