Prepare the Site
Power System Requirements and Specifications
47
Table 13 summarizes the specifications for the cables that you must supply for connecting to 
the power supply terminal studs and grounding studs.
Table 13:  DC Power and Grounding Cable Specifications
Both the grounding studs and each pair of terminal studs on the circuit breaker box are 
spaced at 0.625-in. (15.86-mm) centers. The accessory box shipped with the router includes 
the cable lugs that attach to the end of the power and grounding cables (see Figure 20). The 
spacing of the holes in the lug matches the spacing of the terminal grounding studs. 
Figure 20:  DC Power Supply Terminal and Grounding Lug
During router installation, secure the grounding cable to the grounding studs and the power 
cables to the terminal studs, in that order. Secure the grounding cable lug with washers, then 
with 7/16-in. nuts. Then remove the plastic protective shield that covers the power supply 
terminal studs as shipped, and secure the power cable lugs to the terminal studs with locking 
washers, then with nuts, as shown in Figure 19. Replace the plastic protective shield. The 
nuts and washers that secure the power cables to the terminal studs are already installed on 
the studs.
Cable Type
Quantity and Specification
Maximum Equal 
Length
Power cables
Four 6-AWG (13.3 mm
2
)
 
wire cables 
None
Grounding cable
One 6-AWG (13.3 mm
2
) high-strand-count wire cable
None
For field-wiring connections, use copper conductors only.
For other electrical safety information, see “Electrical 
Safety Guidelines and Warnings” on page 60.
Before router installation begins, a licensed electrician 
must attach the cable lugs to the grounding and power 
cables that you supply. Cables with incorrectly attached 
lugs can damage the router (for example, by causing a 
short circuit). 
Crimp area
6 AWG conductor
All measurements in inches
0.28 
diameter
each hole
2.25
0.25
0.37
0.625
1188
0.55
End view
0.08