Sony BKS-R1601 User Manual

Page of 158
1-4
ROUTING SWITCHER SYSTEM (E)
1-2. System Control
*
1: The transfer speed of BKPF-R70 is 38400 bps.
REMOTE 3 D-sub 25-pin (MODEM side pin arrangement)
Protocol
RS-232C, 9600 bps
*1
, 8bit, No Parity, No check
Function
With this port the communication between the primary station and the control terminal and
the setting of the units are performed. It is recommended that the control terminal be always
connected to the switcher set to the primary station, so that you can see error  message of
the communication circuit and operation condition of units.
Although distorted displays may be shown when a terminal with low access speed is used,
does not mean that the routing system has failed. In this case, replace the control terminal
by one with high access speed. If not, it will be necessary to guess the contents of the
display on the screen.
REMOTE 4 BNC 75 
Z
Z
Z
Z
Z
  47 k
Z
Z
Z
Z
Z
 terminated
Protocol
S-BUS control
Data Transfer Method
BI-PHASE SPACE
Data Transfer Speed
312.5 kbps
Max Cable Length
500 m (BELDEN 8281 cable or equivalent)
FCS Data
HDLC CRC-CCIT 
x
16
 
+ x
12
 
+ x
5
 
+1 Initial all high
Function
Remote port for the monitor S-BUS. It forms a S-BUS data link, different from REMOTE
1, and carries out communication between the primary and secondary stations for the
monitor system (you cannot use this connector for the standard S-BUS). The data link
consists of switchers, remote control units, display units, etc.
To control the monitor S-BUS, the optional monitor board BKDS-V3292B is required.
n
The protocols of REMOTE 2 are selected using the control terminal connected to REMOTE 3.