Sony SIR-3400H User Manual

Page of 156
17-4
 (E)
SIR-3400H / SIR-3032i / SIR-3032W
17-2. Command Details
Setting Commands
All commands use ASCII code. Each command ends with an LF (line feed), CR (carriage return) or CR 
+ LF.
< >: This is the command parameter, and represents one English character.
/[ ]: This enables commands to be specified for individual recording units when multiple recorders are
connected such as during synchronous operation. The / [ ] parameter specifies any one ID number. This
specification can be omitted when only one recording unit is connected or when the target is the recording
unit with ID=0.
When performing synchronous operation with two recording units, the master is ID=0 and the subordinate is
ID=1.
Command
Contents
BAR :
Bar meter control
Command format
BAR : <1><2>/[ ]
<1> : 0=Real-time, 1=Peak hold
<2> : 0=Unidirectional, 1=Bidirectional
Ex.) BAR : 01
Real-time and bidirectional set.
BAR : 11/1
Peak hold and bidirectional set for recorders
Master=0, Subordinate=1.
Related command : BAR?
CAL :
Calibration
Command format
CAL : <1>/[ ]
<1> : 0=Calibration stop, 1=Calibration start
The results can be viewed using the CAL? command.
Related command : CAL?
CHA :
Channel mode setting
Command format
CHA : <1><2>/[ ]
<1> : Analog channel code
<2> : Digital channel code
0=OFF
0=OFF
1=RSV
1=1 ch (Async)
2=RSV
2=2 ch (Async)
3=RSV
3=4 ch (Async)
4=RSV
4=8 ch (Async)
5=16 ch (SIR-1000/1000i)
5=RSV
6=32 ch (SIR-1000/1000i/3400H/3100T)
6=RSV
7=64 ch (SIR-1000/1000i/3400H/3100T)
7=RSV
8=128 ch (SIR-1000/1000i/3400H/3100T) 8=RSV
9=RSV
9=RSV
A=RSV
A=1 ch (Sync)
B=2 ch (SIR-1000W)
B=2 ch (Sync)
C=4 ch (SIR-1000W)
C=4 ch (Sync)
D=8 ch (SIR-1000W)
D=8 ch (Sync)
E=16 ch (SIR-1000W)
E=RSV
F=RSV
F=RSV
n
Analog and digital channel modes can be used together in only certain
combinations.
In this mode, the digital channel can be set.
Related command : CHA?
FMT :
Recording media formatting
Command format
FMT : <1><2><3><4>/[ ]
<1>
: 0=RSV, 1=Formatting start
<2><3><4> : ID number at formatting (001)
n
This command logically erases all pre-recorded data.
Related command : FMT?
FTP :
Frequency type setting
Command format
FTP : <1>
<1> : 0=48 k sampling, 1=65.536 k sampling