REQUIRED CABLE ASSEMBLY OPTIONS:
CBL103: 120V/30A with 10/3 cable 9’ long terminated with a NEMA L5-30P
CBL104: 240V/30A with 10/3 cable 9’ long terminated with a NEMA L6-30P
CBL105: 240V/30A with 3x4.0mm Harmonized cable 9’ long terminated with an IEC 60309 32A plug
This system is designed to be controlled Locally or Remotely via a remote control panel.          SOLD SEPARATELY
SPECIFICATIONS
PC5585-AB
PC5585-AB1/MTD
PC5585-AB/MTD
PC5585-CF
PC5585-CF1/MTD
PC5585-CF/MTD
Approvals
UL/cUL, TUV, CE
UL/cUL, TUV, CE
UL/cUL, TUV, CE
UL/cUL, TUV, CE
UL/cUL, TUV, CE
UL/cUL, TUV, CE
Voltage I/O, (50/60Hz)
120V/240V~
120V/240V~
120V/240V~
120V/240V~
120V/240V~
120V/240V~
Current Input
20A
20A
20A
30A
30A
30A
Current Output
16A
16A
16A
24A
24A
24A
Full Load VA
1920VA/3840VA
1920VA/3840VA
1920VA/3840VA
2880VA/5760VA
2880VA/5760VA
2880VA/5760VA
Circuit Breaker
20/20A
20/20A
20/20A
20/20/30A
20/20/30A
20/20/30A
Multiple Time Delay
Remote only
MTD™ Up
MTD™ Up/Down
Remote only
MTD™ Up
MTD™ Up/Down
Outlets: IEC 60320
Type C13
Type C13 
Type C13
Type C13
Type C13
Type C13 
EMI/RFI Filter
20A
20A
20A
30A
30A
30A
Surge Suppression
270V
270V
270V
270V
270V
270V
RACK MOUNTED
19” x 2U (3.4”) x 8.5” (recessed)
Approximate shipping weight: 18 lbs.
IEC 60320 OUTLETS (14)
12 switched (4 per switched section) on 
the front panel and 2 unswitched on the 
rear panel.  Each outlet is rated by UL    
and CSA at 125V~ / 15A or by VDE at 
250V~ / 10A
REMOTE SELECTION SWITCH
Local: Power “on” to the switched outlets
Off: When breaker is “on” but this switch 
is in the “off” mode, you will have power 
to the unswitched outlets only
Remote: Power “on/off” to the switched   
outlets via a remote device
Latching remote: PC5585-CF1/LT 
only - the selection switch is wired for    
Remote/Off/Remote - There is no local   
control
VOLTAGE SELECTION SWITCH
120V~ Single Phase 50/60Hz
240V~ Single Phase 50/60Hz
EMI/RFI FILTERING
Common Mode Line to Ground
Differential Mode Line to Line
SPIKE/SURGE SUPPRESSION
Line to Line
(3 N/O) REMOTE I/O PORTS
Remote on/off and EPO control, EPO    
overrides remote and local control
Sequence Power Up additional 
equipment down line (standard on all units)
Latching remote - (N/C) EPO, 
momentary start on PC5585-CF1/LT only
POWER INPUT
External terminal block for power input is 
on the rear panel
High Voltage Cover with attached  
 
cable/plug is available, reference below   
part numbers
MULTIPLE TIME DELAY (MTD™) (Optional)
After Section 1 powers up, 4-seconds    
later Section 2 powers up, which is  
 
followed 4-seconds later by Section 3.    
Four seconds later the sequenced remote 
activates the next system in line
Models with (/MTD) sequence power up 
and power down in reverse order
Models with (1/MTD) sequence power    
up but not down
Models without MTD will power up all 12 
switched outlets at once
Sequenced remote is standard on all    
systems
(6) INDICATOR LIGHTS
(1) Main power “on”
(1) Each, Section 1, 2, 3 power “on”
120V~ or 240V~ indicator to show which 
voltage is selected
OVERLOAD CIRCUIT PROTECTION
Electromagnetic breaker provides manual 
on/off switching and trips in an overload 
condition
Front
Back