Panasonic cu-4ks24nbu User Manual

Page of 114
Cooling Characteristics
(RH : 46%, Indoor fan speed : High fan)
(230V, 60Hz)
(1) Low pressure performance chart
(2) Operating current performance chart
(3) Indoor discharge air performance chart
•  This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on 
  the indoor unit type.
•  Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
  (In this case, be sure to stop all the indoor units where performance is not being checked.)
•  The performance is for a tubing length of 24.6t (7.5m). If the tubing length is different, the performance chart will vary.
NOTE
Low pressure at wide tube service valve
psig (MPaG)
Outdoor air temperature °F (°C)
174
(1.2)
188
(1.3)
160
(1.1)
146
(1.0)77
(25)
86
(30)
95
(35)
104
(40)
Lo fan
Hi fan
HH fan
Operating current (A)
Outdoor air temperature °F (°C)
4
5
3
2
Lo fan
Hi fan
HH fan
Indoor discharge air temperature °F (°C)
Outdoor air temperature °F (°C)
46.4(  8)
68.0(20)
64.4(18)
60.8(16)
57.2(14)
53.6(12)
50.0(10)
Lo fan
Hi fan
HH fan
Outdoor Unit   CU-3KS19NBU    Indoor Unit   CS-MKS7NKU ×
1
5-1-1.  Temperature Charts (CU-3KS19NBU)
77
(25)
86
(30)
95
(35)
104
(40)
77
(25)
86
(30)
95
(35)
104
(40)
5.  PERFORMANCE DATA
5-1.  Temperature Charts
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
Indoor air temp. 86°F (30°C)
80°F (27°C)
75°F (24°C)
27