Panasonic cu-4ks24nbu User Manual

Page of 114
No voltage on circuit board
(6) Electric expansion valve
When replacing the electric expansion valve and coil, be sure to attach the connectors in the correct positions. 
Labels are applied to the valve body and coil, corresponding to the connector colors, to identify them.
Controller check
Voltage varies
0 ohm
No temperature change
Temperature changes
Replace the coil.
Open and close the 
electric expansion valve 
by hand to check it.
Replace the electric 
expansion valve.
This part is normal.
Check elsewhere.
Check the illumination 
of the red Power Lamp.
Replace the controller.
Check the coil resistance.
Use a multi-meter to measure the voltage (12 V).
Model No.
Sequence
CU-3KS19NBU
CU-4KS24NBU
CU-4KS31NBU
MV0
MV1
When the power is turned ON, the needle will move in the 
following seguence in approximately 10 to 20 seconds for 
each point.
Check the resistance between the gray lead 
wire and the other wires.
Resistance is OK if it is 46 + / – 4ohm at 68 °F
Cool the main unit with 
a damp cloth or other 
means while welding.
When applying 
vacuum, use the 
special service magnet 
and rotate at least 5 
revolutions 
counterclockwise to 
fully open the electric 
expansion valve.
*1
Approx. 46 +/– 4 ohm
NOTE
*1 If you have manually checked the electric expansion valve, be sure to reapply the outdoor power after you have
    replaced the wiring. (The position of the elecric expansion valve will changed.)
MV2
MV0
MV1
MV2
MV3
Use the special service magnet and 
rotate 5 revolutions clockwise to fully 
close the valve.
Then start the unit and measure the 
temperature at the inlet and outlet 
tubes of the electric expansion valve. 
If the temperature difference is large, 
the valve is closed.
Then rotate 5 revolutions 
counterclockwise to open the valve. 
Operation is normal if the temperature 
difference between the 2 tubes drops.
76