Panasonic cu-ks30nkua User Manual

Page of 108
Valve
Single valve
Charge liquid refrigerant with 
cylinder in up-side-down position.
Single valve (with siphon tube)
Charge with cylinder in normal position.
Liquid
Valve
Liquid
Charging
cylinder
Open
Refrigerant
cylinder
Liquid
NO!
CAUTION
Never charge a large amount 
of liquid refrigerant at once to 
the unit. This may cause 
damage to the compressor.
CAUTION
To prevent the composition 
of R410A from changing, 
never bleed the refrigerant 
gas into the atmosphere 
while transferring the 
refrigerant. (Fig. 3)
(5) Recharging
Be sure to charge the specified amount of 
refrigerant in liquid state using the service port 
of the wide tube service valve. The proper 
amount is listed on the unit's nameplate. 
When the entire amount cannot be charged all at 
once, charge gradually while operating the unit in 
Cooling Operation.
When charging with a refrigerant cylinder, use an 
electronic scale for charging refrigerant. In this 
case, if the volume of refrigerant in the cylinder 
becomes less than 20% of the fully-charged 
amount, the composition of the refrigerant starts 
to change. Thus, do not use the refrigerant if 
the amount in the charging cylinder is less 
than 20%.
Also, charge the minimum necessary amount to 
the charging cylinder before using it to charge 
the air conditioning unit.
Example:
In case of charging refrigerant to a unit requiring 
1.68 lb. (0.76 Kg) using a capacity of a 22 lb. (10 
Kg) cylinder, the minimum necessary amount for 
the cylinder is: 
1.68 + 22    0.20 = 6.08 lb.
(0.76 + 10    0.20 = 2.76 Kg)
For the remaining refrigerant, refer to the 
instructions of the refrigerant manufacturer.
If using a charging cylinder, transfer the specified 
amount of liquid refrigerant from the refrigerant 
cylinder to the charging cylinder. 
Prepare an evacuated charging cylinder 
beforehand.
Do not use the refrigerant if the amount in the 
charging cylinder is less than 20%.
Configuration and characteristics of cylinders
Fig. 1
Fig. 2
Fig. 3
52