Gateway 820 LTO User Manual

Page of 72
16
Chapter 3: Setting Up the Autoloader
www.gateway.com
Choosing a location
Choose a location that meets the following criteria: 
Select a location that is flat, sturdy, level, and close to the host server. Do 
not place the autoloader on the floor or other carpeted surfaces. 
Cabinet (rack) requirements — EIA 310-D standard 19-inch cabinet with 
2U of clearance
Room temperature — 50 to 95ºF (10 to 35ºC) 
Power source — AC power voltage: 100-127 VAC; 200-240 VAC line 
frequency: 50-60 Hz 
Air quality — Minimal sources of particulate contamination. Avoid areas 
near frequently used doors and walkways, stacks of supplies that collect 
dust, printers, and smoke-filled rooms.
Humidity — 20 to 80% RH non-condensing 
Clearance — Back: minimum of 6 inches (15.4 cm). Front: minimum of 
12 inches (30.8 cm). Sides: minimum of 2 inches (5.08 cm). 
Warning
Do not place the autoloader on its side or upside down, 
or stack items that weigh more than 33 lbs. (15 kg) on top 
of the autoloader.
Important
Locate the AC outlet on the back of the autoloader. The 
power cord is the autoloader’s main AC disconnect device 
and must be easily accessible at all times.
Warning
Excessive dust and debris can damage tapes and tape 
drives.
Important
Save all the original packing materials, including the 
accessory box, in case you need to ship or move the 
autoloader at a later time.