The 6000 VA UPS comes in two sections, a Power Module and the Battery Pack.  Each 
unit is RM-3U tall.  The input power is hardwired to the UPS power input terminals.  
The UPS accepts either 208V or 240V input.  The UPS autosenses the input voltage and 
provides the corresponding output voltage (208V or 240V).  The  UPS provides  two 
L6-30R receptacles. 
 
•  Ensure that the UPS Main Circuit Breaker is  open, and the UPS  loads  are 
disconnected while connecting the External Battery Cabinet/s. 
•  Use the battery cable supplied  with the External Battery Cabinet to connect the 
External Battery Cabinet to the UPS.  If more than one battery cabinet is required, 
use the supplied cable.  The batteries will charge automatically when connected to 
the main supply. 
 
NOTE:  The UPS may be used immediately to power a load. However, the 
maximum battery back-up time will not be available until the recommended 8-hour 
minimum charge time has completed. 
 
•  After charging the UPS, connect the load to the UPS.