Toshiba 1000 User Manual

Page of 64
 
 
 
26 
7.7 
UPS Manual Test 
Manual UPS and Battery tests may be performed from the UPS configuration screen. 
Tests may be performed when the battery is not being charged. 
To run the battery test scroll to the “Manual Bat Test” parameter press the Enter button 
twice. 
** Note: In order for the UPS to operate normally, Manual Bypass should always be set 
to OFF because the load will not be protected by the unit when Manual Bypass is ON. 
*** Note: Turn off the UPS and keep the AC power on to use the Generator function. 
(go to normal mode for \Generator\OFF). 
 
7.8 
Interpreting UPS Messages 
Troubleshooting procedures described here provide  instructions  to be used to isolate 
UPS malfunctions. 
Start the troubleshooting procedure in the event of a control panel alarm. 
 
7.9 
Audible Alarms 
•  While operating on battery power (ON BAT LED is on) the UPS will beep once at 
5-second intervals. 
•  While operating on battery power and the battery power is low (ON BAT LED is 
flashing) the UPS will beep twice at 5-second intervals. 
•  In the event of an internal fault with an active alarm (ALARM LED is on), the UPS 
will  provide a constant audible alarm  and display an error message on the LCD 
display. 
•  While operating in the Bypass mode (BYPASS LED is on) the UPS will not beep. 
 
7.10  Silencing an Alarm 
With the exception of a LOW BATTERY Alarm, pressing any of the front panel buttons 
will turn off the alarm. Select Silent Alarm Mode to disable all audible alarms.