Toshiba 431A User Manual

Page of 78
28
 
4300 Series Ancillary Cabinets Installation and Operation Manual
10.5     Anchor the 431A Cabinet
The 431A Cabinet has four mounting holes to anchor the unit after is has been set in place.  See Figure 
10-4. 
Verify the Right Side Access Plate of the 431A and the corresponding left side ac-
cess plate of the 431M or 4300 UPS is removed before anchoring the unit. 
NOTE: Ensure the 431A can be joined to the UPS/431M before final anchoring of the 431A. See below.
Install the anchor bolts to secure the UPS on the floor. See Figure 9-4 for anchor bolt installation detail.
Use 1/2” (12 mm) diameter anchor bolts. There are  four 0.63” (16 mm) diameter holes provided in the UPS 
base. See Figure 8.3 for the hole locations and dimensions for the specified UPS models
If the 431A is joining to the:
 
4300 UPS, go to section 10.6
 
431M, go to section 10.7
Back
Front
4 x 0.63 in. Dia. (16 mm)
19.0 in. (483 mm)
26.7 in..
(677 mm)
Figure 10-4 - 431A Base  
 
        Anchor Points
Anchor Bolt
(1/2 in (12 mm)
4 x 0.63 in. (16 mm) 
diameter bolt holes
4 bolt holes 
(Side View)
Figure 10-3  Anchor Bolt Installation Detail