4300 Series Ancillary Cabinets Installation and Operation Manual
TABLE 12.2 - 431B POWER CABLE SIZES
(
Cable sizes for 75°C Copper Cable)
Recommended/Maximum Wire size and Torque Requirement
UPS  
Rating
Maximum DC 
Current
Batt Cab 
MCCB
Recommended Cable 
Sizes
UPS Terminal 
Lug Tightening 
Torque
431B MCCB Lug
Tightening 
Torque
30 kVA
127 Adc
150 A
#1 AWG – 350 kcmil
200 
lb-in
225 lb-in (25 N•M)
50 kVA
214 Adc
250 A
250 kcmil – 350 kcmil
200 
lb-in
225 lb-in (25 N•M)
* Wire capacity for DC lugs is 350 kcmil - 6 AWG,   
TABLE 12.3 - 431B MCCB CONNECTIONS
Battery Cab 
Capacity
MCCB 
Rating
Lug Cable  
Capacity 
Condutors 
per Lug
Strip 
Length
Lug Torque
30 kVA
150 A
#4 AWG - 4/0
1
1 in.
225 lb-in (25 N•M)
50 kVA
250 A
3/0 - 350 kcmil
1
1 in.
225 lb-in (25 N•M)
Go to Section 12.4  
12.4     Place the 431B Cabinet
The 431B Cabinet has four mounting holes to anchor the unit after is has been set in place.  See Figure 
12-4.  Use 1/2 in (12 mm) bolts to anchor the 431B.
Verify the Left Side Access Plate of the 431B and the corresponding Right side ac-
cess plate of the 4300 UPS are removed before anchoring the unit. 
NOTE: Ensure the 431B can be joined to the UPS before final anchoring of the 431A. Use four 3/8 in.
-16 x 2 in long bolts to bolt the ancillary cabinet frames together.  See Section 12.5.  
Back
Front
4 x 0.63 in. Dia. (16 mm)
19.0 in. (483 mm)
26.7 in..
(677 mm)
Figure 12-4 - 431B Base Anchor Points