12.7     431Bx000xxER111 Backup Runtime Tables 
The following Table 12.4 gives the typical backup runtimes at various loads for a single cabinet 
431Bx000xxER111.
Table 12.4 - 431B Typical Runtimes versus Load
UPS
Capacity
PF
Runtime in Minutes at % Full Load
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
4300
30kVA
0.8
17
21
24
30
38
45
59
>90
>90
>90
4300
30kVA
0.9
15
17
20
24
33
38
53
74
>90
>90
4300
50kVA
0.8
8
9
11
14
17
24
32
46
70
>90
4300
50kVA
0.9
7
8
9
11
15
20
26
44
60
>90