Toshiba G9000 User Manual

Page of 104
 
G9000 Installation and Operation Manual 
 
 
81 
 
Note 3 
 
 
 
 
Note 1 
Note 2 
Code 
indication 
Status message 
Meaning 
Guidance 
Buzzer 
External 
relay contact 
Failure 
lamp 
UF301 
UPS CONTROL 
CIRCUIT ERROR 
AD reference has an abnormal value. 
CALL SERVICE 
ENGINEER 
Continuous 
sound 
Major 
Lit on 
UF302 
UPS CONTROL 
CIRCUIT ERROR 
Detection of an external interruption during 
the software execution. 
CALL SERVICE 
ENGINEER 
Continuous 
sound 
Major 
Lit on 
UF303 
UPS CONTROL 
CIRCUIT ERROR 
Timer does not reset in the specified period 
(WDT settings) 
CALL SERVICE 
ENGINEER 
Continuous 
sound 
Major 
Lit on 
UF305 
UPS CONTROL 
CIRCUIT ERROR 
Detection of an abnormal clock speed in the 
DSP or FPGA.   
CALL SERVICE 
ENGINEER 
Continuous 
sound 
Major 
Lit on 
UF306 
UPS CONTROL 
CIRCUIT ERROR 
Control power supply voltage is below the 
specified level. 
CALL SERVICE 
ENGINEER 
Continuous 
sound 
Major 
Lit on 
UF309 
INVERTER 
VOLTAGE 
ABNORMAL 
Inverter voltage is out of the specified range.  CALL SERVICE 
ENGINEER 
Continuous 
sound 
Major 
Lit on 
UF310 
CONTROL POWER 
SUPPLY 
ABNORMAL 
MMS backup control power supplies exhibit 
abnormal condition. 
CALL SERVICE 
ENGINEER 
Continuous 
sound 
Major 
Lit on 
UF320 
UPS CONTROL 
CIRCUIT ERROR 
Cable disconnection in the parallel interface 
board during load supply. 
CALL SERVICE 
ENGINEER 
Continuous 
sound 
Major 
Lit on 
UF323 
UPS CONTROL 
CIRCUIT ERROR 
Major communication error during parallel 
operation. 
CALL SERVICE 
ENGINEER 
Continuous 
sound 
Major 
Lit on 
UF331 
UPS CONTROL 
CIRCUIT ERROR 
Gate driver abnormal for phase U (Note 4) 
CALL SERVICE 
ENGINEER 
Continuous 
sound 
Major 
Lit on 
UF332 
UPS CONTROL 
CIRCUIT ERROR 
Gate driver abnormal for phase V (Note 4) 
CALL SERVICE 
ENGINEER 
Continuous 
sound 
Major 
Lit on 
UF333 
UPS CONTROL 
CIRCUIT ERROR 
Gate driver abnormal for phase W (Note 4) 
CALL SERVICE 
ENGINEER 
Continuous 
sound 
Major 
Lit on 
UF334 
UPS CONTROL 
CIRCUIT ERROR 
Gate driver abnormal for chopper (Note 4) 
CALL SERVICE 
ENGINEER 
Continuous 
sound 
Major 
Lit on 
UF352 
CONTROL POWER 
SUPPLY 
ABNORMAL 
SMS backup control power supplies exhibit 
abnormal. 
CALL SERVICE 
ENGINEER 
Intermittent 
sound 
Minor 
Flicker 
UF363 
UPS CONTROL 
CIRCUIT ERROR 
Synchronization error signal is being 
received for a considerable time. 
CALL SERVICE 
ENGINEER 
Intermittent 
sound 
Minor 
Flicker 
UF371 
UPS CONTROL 
CIRCUIT ERROR 
Minor communication error during parallel 
operation. 
CALL SERVICE 
ENGINEER 
Intermittent 
sound 
Minor 
Flicker 
UF372 
UPS CONTROL 
CIRCUIT ERROR 
Unable to synchronize the inverter output 
and the bypass voltage when the bypass is 
normal. 
CALL SERVICE 
ENGINEER 
Intermittent 
sound 
Minor 
Flicker 
UF374 
UPS CONTROL 
CIRCUIT ERROR 
Cable disconnection in the parallel interface 
board. 
CALL SERVICE 
ENGINEER 
Intermittent 
sound 
Minor 
Flicker 
UF375 
UPS CONTROL 
CIRCUIT ERROR 
Unable to achieve synchronization for 
parallel operation. 
CALL SERVICE 
ENGINEER 
Intermittent 
sound 
Minor 
Flicker 
UF376 
UPS CONTROL 
CIRCUIT ERROR 
No control response from another UPS 
although its detection is possible. 
CALL SERVICE 
ENGINEER 
Intermittent 
sound 
Minor 
Flicker 
UF377 
UPS CONTROL 
CIRCUIT ERROR 
Overload detection signal is being received 
continuously for a considerable time. 
CALL SERVICE 
ENGINEER 
Intermittent 
sound 
Minor 
Flicker 
UF378 
UPS CONTROL 
CIRCUIT ERROR 
No answer for sending synchronizing signal. 
CALL SERVICE 
ENGINEER 
Intermittent 
sound 
Minor 
Flicker 
UF379 
UPS CONTROL 
CIRCUIT ERROR 
Abnormal clock speed of the parallel control 
board processor. 
CALL SERVICE 
ENGINEER 
Intermittent 
sound 
Minor 