APPENDIX A      Installation Planning Guides (IPG) 
Installation Planning Guide for 80kVA UPS 
Standard System: 480V Input, 480V Output 
 
General Mechanical Information 
Dimensions 
(W    x D x H) 
Weigh
Floor 
Loading 
Approximate Full-Load 
Heat Rejection 
Mechanical Clearance (Inches)from UPS 
for Ventilation and Maintenance Access 
Inches 
Lbs. 
Lbs./ft.
 2
 
Btu/Hr 
Top 
Front 
Bottom 
Sides** 
Back 
27.6” x 32.8” x 80.6”* 
855 
136 
10,771 
20” 
40” 
0” 
0” 
0” 
* Height includes removable fan housing – Frame height is 78.7”. 
** 0” clearance for peripheral equipment, 1” clearance for walls. 
 
Primary AC Input (480V 3-Phase / 3-Wire) 
Maximum Input Power Demand 
Normal Mode (Recharge Mode) 
Suggested External 
Overcurrent Protection 
External Feeder Wire Size:    Min. – Max. Per Phase 
kVA 
PF 
Amps 
Amps 
AWG or kcmil at 75º C Temp. Rating 
76 (80) 
>0.99 
91 (97)   
125 AT 
#1 – 1/0   
 
Alternate (Bypass) AC Input (480V 3-Phase / 3-Wire) 
Maximum Input Power 
Demand 
Suggested External 
Overcurrent Protection 
External Feeder Wire Size:     
Min. – Max. Per Phase   
kVA 
PF 
Amps 
Amps 
AWG or kcmil at 75º C Temp. Rating 
80 
0.9 
96 
125 AT 
#1 – 1/0   
 
Battery Input (480VDC Nominal) 
Battery Capacity Required 
for Full Load Output 
Maximum Discharge 
at Full Load Output 
Suggested External 
Overcurrent Protection 
External Feeder Wire Size:    Min. – Max. 
 
kWB 
Amps DC 
Amps 
AWG or kcmil at 75º C Temp. Rating 
75 @ 0.9 PF 
188 
200 AT 
3/0 – 250 kcmil 
 
AC Output (480V 3-Phase / 3-Wire) 
Rated Output Power 
Suggested External 
Overcurrent Protection 
External Feeder Wire Size:     
Min. – Max. Per Phase   
kVA 
PF 
Amps 
Amps 
AWG or kcmil at 75º C Temp. Rating 
80 
0.9 
96 
125 AT 
#1 – 1/0   
 
Important Notes: 
 
1.  Maximum input current is limited to 106% of the full-load 
input current. 
2.  Output load conductors are to be installed in separate 
conduit from input conductors. 
3.  Control wires and power wires are to be installed in separate 
conduits. 
4.  Recommended AC input and output overcurrent protection 
based on continuous full load current per NEC. 
5.  Wiring shall comply with all applicable national and local 
electrical codes. 
6.  Grounding conductors to be sized per NEC Article 250-122.  
Neutral conductors to be sized per NEC Article 310.15. 
- Primary AC Input: 3
φ, 3-wire + ground. 
- Alternate AC Input: 3
φ, 3-wire + ground. 
- AC Output: 3
φ, 3-wire + ground. 
- DC Input: 2-wire (Positive/Negative)    + ground. 
7.  Nominal battery voltage based on the use of VRLA type 
batteries (2.0 volts/cell nominal). 
8.  Maximum battery discharge current based on lowest 
permissible discharge voltage of 1.67 VPC. 
9.  DC wires should be sized to allow not more than a 2-volt 
drop at maximum discharge current. 
10. Weights do not include batteries or other auxiliary equipment 
external to the UPS. 
 
11.  Cable sizing calculations based on the following assumptions: 
-  Minimum size is smallest size based on ampacity at 30 
°C. 
-  Maximum size cable is based on cable bend radius 
limitations at the UPS terminals. 
-  Not more than 3 current-carrying conductors installed in 
conduit in ambient temperature of 30 
°C. 
-  Temperature rating of copper conductors/terminals: 75 
°C. 
-  Reference: 2005 NEC Handbook, Table 310.16.   
NOTE:    Consult latest edition of applicable 
national and local codes for possible 
variations. 
12.  Ratings of wires and overcurrent devices are suggested 
minimums.    Consult with a registered Professional Engineer 
within your local area for proper size selections. 
 