6.2 Zero Adjustment 
To conduct zero adjustment of the flowmeter, the fluid in the detector pipe must be held still
There are three different ways to start the zero adjustment:   
(1) Pressing a combination of control keys for the model with LCD display 
   
See 8.2.14 “Still Water Zero Adjustment” 
(2) Sending a command signal from a HART communications device (a communication   
device such as hand-held terminal AF900 is required) 
   
See the instruction manual of hand-held terminal you use. 
(3) PROFIBUS communication (a communication device for PROFIBUS is required) 
   
See the instruction manual of communication device you use. 
Note 1: If the detector pipe is not filled with the fluid to be measured, the flow rate will be 
indefinite and unable to be measured. Before using the flowmeter, be sure to fill the 
detector pipe the fluid to be measured.