8.2.15 Manual Zero Adjustment 
 
This function is used to perform zero adjustment simply by comparing the output value of the converter 
with the process value of other instruments without stopping the process of measurement. 
If zero adjustment described in 8.2.14, “Still Water Zero Adjustment” can be performed, this 
manual setting is not needed. 
 
● Changing the manual zero adjustment value 
Calculate the adjustment value with the following equation: 
 
Adjustment value (%) = {(Actual flow rate) 
− (Converter’s measured value)} 
 
* Calculate the manual zero value using the % value for the setting range (Range 1) of the converter. 
See the following example. 
 
(Example) 
 
Flow rate 
% value to setting span 
Actual flow rate obtained 
from other instrument 
10.0 m
3
/min
50.0 % 
Converter’s measured value 
10.5 m
3
/min
52.5 % 
Manual zero adjustment value
 
-2.5 % 
(If manual zero adjustment value is set to +2.5 %, the converter output is shifted by 
−2.5% 
and the output of 50.0 % will be obtained.) 
 
The following is an example to change the manual zero adjustment value from +1.0% to 
−2.5%. 
Switch operation 
Display example 
Description 
 
F:ZERO 
1 ZERO ADJ 
2 MANUAL
 
3 EXIT 
 
 
Select "MANUAL" from the setting item 
selection menu. 
STEP1 
 
 
 
MANUAL 
 
    +001.0 
 
         % 
 
 
 
The currently set manual zero value (+1.0% 
in this example) appears. 
 
Then push              . 
 
STEP2 
 
 
 
MANUAL 
 
    
+
001.0 
 
         % 
 
 
 
The switches at the bottom change. 
(                                      are shown.) 
At the same time, the cursor appears. 
 
 
 
ESC 
ESC