Emerson 3000 User Manual

Page of 88
Water-Cooled Models—Self-Contained Compressor
39
Liebert
®
 Challenger 3000
4.3
Water Regulating Valve
The water regulating valve automatically regulates the amount of fluid necessary to remove the heat 
from the refrigeration system, permitting more fluid to flow when load conditions are high and less 
fluid to flow when load conditions are low. The valve consists of a brass body, balance spring, valve 
seat, valve disc holders, capillary tube to discharge pressure, and adjusting screw.
4.3.1 Standard Valve - 150psig (1034kPa) System for 3 & 5-Ton Units (Johnson Controls Valve)
High Pressure Valve - 350psig (2413kPa) System for 5-Ton Units (Johnson Controls Valve)
Adjustment
The valve may be adjusted with a standard refrigeration service valve wrench or screw driver.
To lower the head pressure setting, turn the square adjusting screw clockwise until the high pressure 
gauge indicates the desired setting.
To raise the head pressure setting, turn the adjusting screw counterclockwise until the desired 
setting is obtained.
Figure 21 Johnson Controls valve adjustment
Range 
spring
Valve spring 
guide
Top 
retainer
Range adjustment screw
Insert screwdrivers underneath 
the valve spring guide