Schneider Electric MGE Galaxy 5000 User Manual

Page of 17
APC by Schneider Electric 
 
MGE GALAXY 5000  
 
Data Center Grade Three Phase Uninterruptible Power Supply 
 
Parallel Module - Guide Specifications 
40-130 kVA UPS  
 
 
 
1.0    GENERAL
 
 
1.1 SUMMARY 
 
This specification describes a three-phase, on-line, double conversion, solid state Uninterruptible 
Power System hereafter referred to as the UPS.  The UPS shall operate in conjunction with the 
existing building electrical system to provide high quality power conditioning, back-up power 
protection and distribution for electronic equipment loads. The system shall consist of a solid state  
IGBT rectifier/inverter, power factor corrected rectifier, a 100% rated for continuous duty static 
switch, battery plant, graphical status/control panel, and synchronizing circuitry as described herein. 
 
1.2 STANDARDS 
 
 
The UPS shall meet the requirements of the following standards: 
 
A.  UL listed under 1778, standards for uninterruptible power supply equipment 
B.  UL Canada (cUL) 
C.  FCC rules and regulations of part 15, subpart J, class A 
D.  IEC 1004/ANSI C62.41 Standards for Surge Withstand Ability 
E.   ISO 9001 
F.  The UPS shall be designed in accordance with the applicable sections of the documents 
published by: 
 
  National Fire Protection Association (NFPA)/National Electric Code (NEC) 
  National Electrical Manufacturer’s Association (NEMA) & (NEMA PE 1) 
  Occupational Safety & Health Administration (OSHA) 
 
1.3 SUBMITTALS 
 
Submittals shall contain the following documentation:  
 
A.  Installation Package: Complete electrical characteristics and connection requirements. 
 
Provide detailed equipment outlines with cabinet dimensions and spacing requirements; 
location of conduit entry/exit paths; location of floor/seismic mounting; available battery 
types/sizes; all cabinet weights; heat rejection and air flow requirements; single-line diagram; 
control and external wiring. 
 
B.  Product Data:  Provide catalog sheets and technical data sheets to indicate physical data and 
electrical performance, electrical characteristics, and connection requirements. 
 
C.  Manufacturer’s Installation Instructions:  Indicate application conditions and limitations of 
use stipulated by Product testing agency.  Include instructions for storage, handling, protection, 
examination, preparation, installation, and starting of Product.  Include equipment installation 
 
 
APC – MGE Galaxy 5000 Specification  (60Hz) 
1
 
Effective:  June 1, 2008 REV X0 JJG 
Parallel Module