temco-tool 36rdvdsn User Manual

Page of 44
8
RDVDSN Series Direct Vent Gas Fireplace
20007894
The fireplace, when installed, must be 
electrically connected and grounded in 
accordance with local codes or, in the ab-
sence of local codes, with the current CSA 
C22.1 Canadian Electrical Code.
For USA installations follow local codes 
and the national electrical code  ANSI/
NFPA No. 70.
It is strongly suggested that the wiring of 
the EB-1 Electrical Junction Box be carried 
out by a licensed electrician.
Ensure that the power to the supply line 
has been disconnected before commenc-
ing this procedure.                
When purging gas line, the front window 
frame assembly must be removed.
1.  The gas pipeline can be brought in through the rear 
of the fireplace as well as the bottom. Knockouts are 
provided on the bottom behind the valve to allow for 
the gas pipe installation and testing of any gas con-
nection. It is most convenient to bring the gas line in 
from the rear right side of the valve as this allows fan 
installation or removal without disconnecting the gas 
line.
  The gas line connection can be made with prop-
erly tinned 3/8” copper tubing, 3/8” rigid pipe or an 
approved flex connector. Since some municipali-
ties have additional local codes, it is always best to 
con-  sult your local authority and the National Fuel 
Gas Code, ANSI Z223.1/NFPA 54 in the USA or the 
CSA-B149.1 installation codes.
*Adhere to the following installation requirements in the State 
of Massachusetts:
 
The installer must be a licensed plumber or gas fitter.
 
Flex connectors must be Massachusetts approved, cannot 
exceed 36” (914 mm) in length, must be a minimum 1/2” 
dia. and may not penetrate a wall.
2.  The gas control inlet is 3/8” NPT. typical installation 
layout for rigid pipe is shown in Figure 8.
  NOTE: All models are equipped with a flex tube 
with a shut off valve having a 1/2” NPT inlet. The 
flex line with shut off is shipped in the control 
valve compartment. Using two wrenches, tight-
en the flexible tube at the shut off valve and at 
the gas control
3.  When using a flex connector,* use only approved 
fittings. When a union is installed, provide easy 
access in its placement for servicing. Refer to gas 
specification for pressure details and ratings.
4.  When a vertical section of gas pipe is required for 
the installation, a condensation trap is needed. In 
Canada see CSA-B149.1 for code details. See the 
National Fuel Gas Code ANSI Z223.1/NFPA 54 in 
the USA.
Gas Line Installation
1/2” Gas Supply
FP297A
INSTA VENT FREE
UVHB26 GAS SUPPLY 
7/1/98
FP297A
1/2” NPT X 3/8” Flare Shut-off Valve
3/8” Flex line 
(from valve)
Fig. 5  Typical gas supply installation.
5.  For natural gas, a minimum of 3/8” iron pipe with a 
gas supply pressure of 4.5” w.c. (from the gas me-
ter). Consult with local gas utility and ANSI Z223.1/
NFPA 54 if any questions arise concerning pipe 
sizes.
6.  Turn the gas supply to ‘ON’ and check for leaks. DO 
NOT USE OPEN FLAME FOR THIS PURPOSE. 
Use an approved leak testing solution.
7.  The appliance and its appliance main gas valve 
must be disconnected from the gas supply piping 
system during any pressure testing of that system at 
test pressures in excess of 1/2 psig (3.5K Pa).
8.  This appliance must be isolated from the gas supply 
piping system by closing its equipment shut off valve 
during any pressure testing of the gas supply piping 
system at test pressures equal to 1/2 psig (3.5K Pa).
Always check for gas leaks with a mild 
soap and water solution. Do not use an 
open flame for leak testing.
When using copper or flex connector use only approved 
fittings. Always provide a union when using black iron 
pipe so that the gas line can be easily disconnected 
for burner or fan servicing . See gas specifications for 
pressure details and ratings.
The fireplace valve must not be subjected to any test 
pressures exceeding 1/2 psi. Isolate or disconnect this 
or any other gas appliance control from the gas line 
when pressure testing. 
EB-1 Electrical Box