APC mgetm galaxytm 6000 User Manual

Page of 46
6739381EN/
Rectifier-inverter cubicles
Characteristics of rectifier-inverter cubicles
rated
cubicle
cubicle
cubicle
maximum
inverter
width W
height H
depth D
weight
output
in mm (1)
in mm
in mm
in kg
in kVA
250
1600
1900 ± 10
840
1650
300
1600
1900 ± 10
840
1650
400
1600
1900 ± 10
840
2030
450
1600
2000 ± 10
840
2070
500
1600
2000 ± 10
840
2205
600
3600
1900 ± 10
840
3500
Characteristics of Static Switch Cubicles
rated
cubicle
cubicle
cubicle
maximum
heat
SSC
width W
height H
depth D
weight
losses (2)
output
in mm (1)
in mm
in mm
in kg
in kVA
in kW
in cal./s
500
1000
1900 ± 10
840
350
2.9
696
800
1000
1900 ± 10
840
500
3.7
888
1200
1600
1900 ± 10
840
1000
< 0.5
< 120
2000
2450
1900 ± 10
840
1710
< 0.5
< 120
Static Switch cubicles
The parameters given in the table
opposite can be used to determine the
required rating of a single-unit or
modular UPS, a frequency converter, or
a parallel UPS with SSC.
Characteristics of external maintenance bypass cubicles
(Modular UPS with external maintenance bypass)
rated
cubicle
cubicle
cubicle
maximum
bypass
width W
height H
depth D
weight
in kVA
in mm (1)
in mm
in mm
in kg
1200
1200
1900 ± 10
840
450
External maintenance bypass cubicles
Characteristics
 (cont.)
When installing several cubicles, allow for a tolerance of 0/+3mm per metre.
(1) 25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This
applies to all cubicle installation cases.
(1) 25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This
applies to all cubicle installation cases.
When installing several cubicles, allow for a tolerance of 0/+3mm per metre.
(1) 25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This
applies to all cubicle installation cases.
When installing several cubicles, allow for a tolerance of 0/+3mm per metre.
"Pack Advance" cubicles
Characteristics of "Pack Advance"Cubicles
rated
cubicle
cubicle
cubicle
maximum
heat
SSC
width W
height H
depth D
weight
losses (2)
output
in mm (1)
in mm
in mm
in kg
in kVA
in kW
in cal./s
300
400
1900 ± 10
840
335
2.9
696
400
400
1900 ± 10
840
440
3.7
888
450
400
1900 ± 10
840
440
< 0.5
< 120
(1) 25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This
applies to all cubicle installation cases.
When installing several cubicles, allow for a tolerance of 0/+3mm per metre.