GE LTC MAP User Manual

Page of 68
 
70055MP Revision D 
February 3, 2000 
Section 5: Troubleshooting Procedures 
Refer to Table 5-1 for common troubleshooting procedures. 
Table 5-1: Common Troubleshooting Procedures 
Condition 
Possible Cause(s) 
Corrective Action 
Incorrect Temperature Reading on a 
4-20 mA Channel. 
Defective sensor. 
 
Loose wiring connection from sensor 
to circuit board 
 
 
Defective circuit board. 
 
Ribbon cable between CPU and I/O 
circuit boards loose. 
 
 
 
 
Ground loop exists with another 
connection. 
 
Swap suspect sensor with a known good sensor. 
Check wiring connection from the sensor to the 
circuit board; ensure that the wire is correctly 
inserted into the screw down connector block. 
Swap suspect circuit board with a known good 
board. 
Temporarily move the suspect RTD sensor wire to 
an unused 4-20 mA channel to determine 
whether fault follows sensor or circuit board. 
Inspect ribbon cable connection at CPU board and 
at I/O board. 
Systematically remove other connections to the 
circuit board until the cause of the loop is found.  
For example, problems may be caused having 
the individual wire (color) order incorrect for the 
cable between the control isolator and the I/O 
board. 
Unrecorded tap change events. 
Incorrect wiring. 
Incorrect parameter settings. 
Check wiring diagram and installation. 
Check event start and stop parameters. 
Check for a minimum motor current parameter. 
Incorrect Current Readings. 
Incorrect installation. 
No current present. 
Incorrect parameter settings. 
Check wiring diagram and installation. 
Verify current with a handheld meter. 
Check CT Ratio. 
Check Calibration Parameters. 
Incorrect Voltage Readings. 
Incorrect wiring. 
Incorrect parameter settings. 
Power glitch. 
Check wiring diagram and installation. 
Check Calibration Parameters. 
Cycle Power.